Specifications
Configuring Trend Set Displays
PlantScape Server and Client Configuration Guide 231
Trend Set Display Types
The following standard Trend Set displays are available:
Related Display Types
The Trend Set displays complement other types of trend displays that are used to
view historical data:
Single Trend Used to display a bar graph of historical data for a single
point
Dual Trend Used to display bar graphs of historical data for two points
Triple Trend Used to display bar graphs of historical data for up to three
points
Multiplot Trend Used to display a line graph of historical data for up to eight
points
Multirange Used similarly to the Multiplot Trend but enables the display
range of each of the eight points to be individually configured
X-Y Plot Used to display an X-Y plot of the historical data for two
analog points with one point’s values plotted against the
others
Numeric Trend Used to display a list of the historical data for up to eight
points in a numerical format
Detail Trend display Accessible directly from a Point Detail display. It requires
no configuration and shows a bar graph display of
historical information for a single point.
Group Trend displayAccessible from a Group Detail display. Once the group
itself is configured, no configuration of the Group Trend
display is required. It gives a multi-plot trend of the points
in the group. The points can be trended and controlled
from the same display. This enables the downstream effect
of point controls on cascaded functions to be observed on
a single display.
To call up an Group Trend display, click the View Trend
link in the bottom right corner of the relevant Group
Configuration display.
Custom Trend
display
Trends can be added to custom displays. For details, see
the Display Building Guide.