Specifications

Configuring Alarm Paging
PlantScape Server and Client Configuration Guide 199
Configuring Alarm Paging
You can configure a number of characteristics of the Alarm Paging system. For
example, you can:
Select the connection method, either to a paging system or by modem to a
paging service provider.
Enter information regarding modem or paging system connections and set a
password.
Configure communications settings.
View the alarm paging status.
Enable or disable the pager service.
View the number of alarms in the alarm queues and clear the queue if
necessary.
Set up escalation, so that paged alarms are automatically sent to another
pager if they are not acknowledged within a specified time.
Determine the information you include in the alarm messages you want the
pagers to receive.
Configure the escalation delay and the delay to page times, to allow time for
alarms to be acknowledged before they are paged out.
Only people with a security level of SUPV or higher can configure or change the
settings for Alarm Paging.
Alarm Paging Configuration Sequence
It is important to configure Alarm Paging in the correct sequence. For example, a
pager must be set up before it can be nominated to receive pager output. Each
step in the configuration should be completed before the next is begun.
The configuration sequence is as follows:
1
Connect the modem or paging system to a serial port on the server and
configure modem connection details.
2
Configure paging service provider details (including dialing and
communication settings).
3
Configure each pager to be used with the system.
4
Nominate the alarms to be paged, the pagers they are to be sent to, and any
escalation.
plscpcg.book Page 199 Monday, May 28, 2001 10:11 AM