Specifications
History Collection and Archiving
PlantScape Server and Client Configuration Guide 169
Gating Points, Parameters, and States
To avoid collecting inaccurate historical data (for example, a zero error on a flow
transmitter when the associated valve is closed or the pump off), you can define
the conditions under which data should be collected. You do this as follows:
1
Select a gating point from the drop-down list of points.
2
Select a parameter from the drop-down list of parameters.
3
Specify the state for that gating point in the State field.
For example, for a point monitoring a flow, you would probably only want to
collect history when the pump is running. In this case you would define:
• The gating point as the point ID of the point that monitors the pump
• The state of the gating point as ON (or whichever wording you have
configured for that state of the PV)
Note A history sample is still collected regardless of the gating state.
When the gate point is not in the gate state, the history samples for the point
are saved as a “bad value” and therefore will not affect history averages that
are calculated from the snapshots.
Viewing History Collection Configuration
You can view the points configured for history collection by selecting Configure
⇒
History
⇒
History Assignment to call up the History Collection displays.
Extended History 1-hour snapshot 7 days 170
8-hour snapshot 3 months 281
24-hour snapshot 1 year 368
Fast History 1 - 30-second
snapshot
1 hour 3670 - 122
History Types Intervals Default Retention Period
Duration Number of Samples
Table 8.3 Default Retention Periods (Continued)
plscpcg.book Page 169 Monday, May 28, 2001 10:11 AM