Specifications

8 – Configuring Points
160 R400
Transmitter High
A Transmitter High alarm is similar to the PV High alarm. It can be used to
indicate a failed transmitter signal.
For each alarm, you can also specify the alarm priority, sub-priority and the
specific limit. Alarm priorities and sub-priorities are described in “Defining
Events, Alarms, and Alarm Priorities” on page 162. Alarm limits are described
below.
Alarm Limit
You use the Limit field for each alarm type to specify the value (in engineering
units) at which the alarm should be generated.
Unreasonable Low and Unreasonable High Alarms for Analog Points
In addition to the previous alarm types, you can also configure a set of alarms for
an unreasonable high value and an unreasonable low value for the PV of an
analog point.
To define these alarms, you need to use Station as well as Quick Builder:
You use Station to define the unreasonable high and unreasonable low limit
values.
You use Quick Builder to define the alarm priority and sub-priority for
unreasonable values for each point.
Using Station
The “unreasonable high” and “unreasonable low” values are server-wide settings
that you specify on the Point Processing tab of the Alarm & Point Processing
display on a Station. See “Server-Wide Point Configuration” on page 186 for
details.
Using Quick Builder
Use the Alarm property sheet to enable unreasonable value alarms as follows:
1
Select an alarm priority (other than None) from the Priority list for the
Unreasonable Value field.
2
Specify a sub-priority for the alarm in the Sub Priority field.
Alarm priorities and sub-priorities are described in “Defining Events, Alarms, and
Alarm Priorities” on page 162.
plscpcg.book Page 160 Monday, May 28, 2001 10:11 AM