Specifications
Main Properties
PlantScape Server and Client Configuration Guide 143
PVAlgoExists If set (=1), a PV algorithm has been
built on the point.
301
✔✔✔
ActionAlgoExists If set (=1), an Action algorith has
been built on the point.
302
✔✔✔
PointInAlarm The point is in alarm (0=no alarm,
1=in alarm)
303
✔✔✔
InRateOfChangeAlarm If set (=1), a Rate of Change alarm
exists.
304
✔✔
InDeviationLowAlarm If set (=1), a Deviation Low alarm
exists.
305
✔
InDeviationHighAlarm If set (=1), a Deviation High alarm
exists.
306
✔
InTransmitterLowAlarm If set (=1), a Transmitter Low alarm
exists.
307
✔
InTransmitterHighAlarm If set (=1), a Transmitter High alarm
exists.
308
✔
InLowAlarm If set (=1), a PV Low alarm exists. 309
✔
InHighAlarm If set (=1), a PV High alarm exists. 310
✔
InLowLowAlarm If set (=1), a PV Low Low alarm
exists.
311
✔
InHighHighAlarm If set (=1), a PV High High alarm
exists.
312
✔✔
InUnreasonablyLowAlarm If set (=1), an Unreasonably Low
alarm exists.
313
✔
InUnreasonablyHighAlarm If set (=1), an Unreasonably High
alarm exists.
314
✔
ModeCheckDisabled If set (=1), the mod is not checked
before doing a control.
319
✔✔
A1AssociatedParameter If non zero, the A1 value is store to
this parameter.
320
✔
A2AssociatedParameter If non zero, the A2 value is store to
this parameter.
321
✔
Internal Parameter Description
ID
Status
Analog
Acc.
Table 8.2 Internal Point Parameters