Specifications
8 – Configuring Points
142 R400
State5AlarmEnabled State 5 is an alarm state. 125
✔
State6AlarmEnabled State 6 is an alarm state. 126
✔
State7AlarmEnabled State 7 is an alarm state. 127
✔
NumberOfInputStates Number of Status PV states (2, 4, or
8)
129
✔
NumberOfOutputState Number of Status OP states (2 or 4) 130
✔
NormalMode The normal mode of the point, for
example, Auto.
131
✔✔
PulseWidthSecs For a status OP, if this is non zero,
the OP will be reset to zero after this
time.
132
✔
OPReverse The OP value is reversed. 133
✔✔
ControlConfirmRequired If enabled (=1), the operator must
confirm all changes to the point.
134
✔✔
ControlTimeout An index to a system table that
specifies the time in seconds that a
control takes to complete.
135
✔✔
DriftDeadbandPercent The value must change by more
than this amount to be considered a
change.
136
✔
AlarmDeadbandPercent The value must drop below the
alarm limit by this amount before
the alarm is returned.
137
✔✔✔
ControlDeadbandPercent The value gets this close to the
target value, the control is
considered complete.
138
✔
PVClampingEnabled If enabled (=1), the PV will be
clamped to the EULO and EUHI
settings.
139
✔
PointDetailDisplayDefault The default detail display for the
point type.
200
✔✔✔
GroupDetailDisplayDefault The default group display for the
point type.
201
✔✔✔
Internal Parameter Description
ID
Status
Analog
Acc.
Table 8.2 Internal Point Parameters