Specifications

8 – Configuring Points
142 R400
State5AlarmEnabled State 5 is an alarm state. 125
State6AlarmEnabled State 6 is an alarm state. 126
State7AlarmEnabled State 7 is an alarm state. 127
NumberOfInputStates Number of Status PV states (2, 4, or
8)
129
NumberOfOutputState Number of Status OP states (2 or 4) 130
NormalMode The normal mode of the point, for
example, Auto.
131
✔✔
PulseWidthSecs For a status OP, if this is non zero,
the OP will be reset to zero after this
time.
132
OPReverse The OP value is reversed. 133
✔✔
ControlConfirmRequired If enabled (=1), the operator must
confirm all changes to the point.
134
✔✔
ControlTimeout An index to a system table that
specifies the time in seconds that a
control takes to complete.
135
✔✔
DriftDeadbandPercent The value must change by more
than this amount to be considered a
change.
136
AlarmDeadbandPercent The value must drop below the
alarm limit by this amount before
the alarm is returned.
137
✔✔✔
ControlDeadbandPercent The value gets this close to the
target value, the control is
considered complete.
138
PVClampingEnabled If enabled (=1), the PV will be
clamped to the EULO and EUHI
settings.
139
PointDetailDisplayDefault The default detail display for the
point type.
200
✔✔✔
GroupDetailDisplayDefault The default group display for the
point type.
201
✔✔✔
Internal Parameter Description
ID
Status
Analog
Acc.
Table 8.2 Internal Point Parameters
plscpcg.book Page 142 Monday, May 28, 2001 10:11 AM