Specifications

8 – Configuring Points
136 R400
AlarmType8 The type of alarm 8, for example,
PVHI
25
✔✔
RollOver Accumulator input rollover value,
for example, a 12 bit counter rolls
over at 4095.
26
MeterFactor The accumulator meter factor.
Normally 1.0, is adjusted after meter
proving.
27
ScaleFactor The accumulator scale factor, for
example, 1 pulse.count = 5.678
liters.
28
RawPV The value of the accumulator raw
input (the counter it is reading).
29
SetpointLowLimit Data entry of Setpoint values below
this value will be rejected.
32
SetpointHighLimit Data entry of Setpoint values above
this value will be rejected.
33
OutputLowLimit Data entry of Outpoint values
below this value will be rejected.
34
OutputHighLimit Data entry of Outpoint values
above this value will be rejected.
34
LastProcessedDate The day when the value of the PV
last changed.
38
✔✔
LastProcessedTime The time of day when the value of
the PV last changed.
39
✔✔
H1M History Standard 1 min 41
✔✔✔
H6M History Standard 6 min 42
✔✔✔
H1H History Standard 1 hour 43
✔✔✔
H8H History Standard 8 hour 44
✔✔✔
H24H History Standard 24 hour 45
✔✔✔
H5SF History Fast 5 second. Configurable
between 1 and 30 seconds.
46
✔✔✔
H1HE History Extended 1 hour 47
✔✔✔
Internal Parameter Description
ID
Status
Analog
Acc.
Table 8.2 Internal Point Parameters