Installation Instructions

Table Of Contents
1
500-33050_2
PDB-8C1R and 8F1R
Power Distribution Boards
Distributed Power Control Interface for Fire, Access, HVAC, Elevator, and Security
Features:
8 Power Limited Outputs with Auto-Resetting
Circuit Breakers for model 8C1R
Each Output is Individually Selectable to
Turn On, Turn Off, or always ON when Triggered
Outputs can be triggered with:
1. Voltage or Reverse polarity (optically isolated)
2. N/O or N/C switch with supervised EOL
Form C Contacts (TRIGGERED) and Red LED (TRG)
Indicate Trigger Status
Form C Contacts (TROUBLE) and Green LED (TRB)
Indicate:
1. One of the output circuit breakers is tripped
Main Fuse Blown or no power on input
Operates with 12-28VDC; Nominal 12-24VDC
Each Output pair has a Removable Terminal Block
Each Output has a Green Status LED
Main Power has Green Status LED
Main Power Pull and Fuse
Lifetime Warranty
UL Listed Sub Assembly for Access Control and Burglar Alarm Systems
Description
The PDB-8C1R power distribution control interface converts a main non-power limited DC power source to 8 power-limited
outputs that can be controlled by a (FACP) Fire Alarm Control Panel. For the model PDB-8C1R /8F1R each output can be
selectively set (J1-J8) to turn ON or to Turn OFF when triggered by the panel. The FACP or other control system can interface to
the PDB-8C1R /8F1R with either of two or both supervised trigger inputs. One trigger is activated with a reverse polarity voltage
from a FACP. This trigger is fully isolated with an optical isolator. The other trigger is an (EOL) 2.2K End Line Resister input which
will accept a (N/O) Normally Open switch or a (N/C) Normally Closed switch.
When triggered, the Trigger Transfer Relay removes power from the NORM + bus and transfers it to the TRIG + bus. Jumpers J1-
J8 determines which bus each output is connected to. The triggered form C contacts also drop off normal when triggered and
the Red (TRG) LED turns on. These contacts can be used to daisy chain other PDB-8C1R, latch, or provide feedback to a system.
The Trouble Form C Relay drops off Normal if any one of the PTC circuit breakers is tripped, or main power/fuse is lost. The Green
(TRB) LED is ON during normal operation, it goes off with trouble. All three relays are Fail-Safe, energized in the normal
condition.
Each output has a Green LED that is on when the associated output (-1+ through -8+) is ON.
Typical applications for a Fire Alarm System would include adding remote Bells and enunciators, closing dampers, turning off
HVAC fans, unlocking fail secure and fail safe doors, and or returning elevators to first floor.
Note: HVAC and Elevator Control has not been evaluated by UL