TROUBLESHOOTING A MAGNALOCK
CHALLENGE SOLUTION
Lock does not generate a
magnetic field
CHECK for specified voltage at Magnalock.
CHECK for specified current draw at Magnalock.
Reduced holding force
CHECK DC power source is Full-Wave Rectified
(Half-wave Rectifier or AC Power unacceptable).
CHECK for specified voltage at Magnalock.
CHECK for specified current draw at Magnalock.
CHECK strike mounting for proper installation.
CHECK the Magnalock and strike for obstructions
and that contact surfaces are properly cleaned.
BondSTAT does not report
secure
CHECK for specified voltage at Magnalock.
Check for specified current draw at Magnalock.
CHECK strike mounting for proper alignment and
pivoting for proper closure to Magnalock.
CHECK the Magnalock and strike for obstructions
and that contact surfaces are properly cleaned.
DPS does not report door
status
CHECK strike mounting for proper alignment.
CHECK for proper door closure.
CHECK for proper voltage/current on switch.
CHECK resettable protection device.
Magnalock does not release
ENSURE no voltage is present at Magnalock.
ENSURE the Magnalock is not drawing current.
CHECK if the strike is sticky and hard to release.
CHECK the Magnalock and strike for obstructions
and that contact surfaces are properly cleaned.
Magnalock is dirty or rusty ENSURE the Magnalock is properly cleaned.