Installation Manual
AQM20 Series Installation Instructions
AQM20 Series Instructions Doc.# 500-33010 Rev. B
Page 5 of 9
PDB-8C / PDB-8F
Multi Output
Low Voltage Power Distribution Modules
Life Time Warranty
Features/Specifications:
Converts a single AC or DC (12 or 24v) Input to 8 or 16 protected outputs with
fuses or circuit breakers
1500 Watt surge protection on PDB-8F Input rated 22 Amps @ 32 volts AC or
DC
All PTC circuit breaker ratings are holding current at 130
o
F per UL Standards
Main Power Green/Red LED Indicates AC, DC or Reversed DC Input on PDB-
8 and PDB-9
Each output has a green status LED indictor
Current Draw is 6ma max per LED
Main Fuse / Power Pull is standard ATO Automotive size on PDB-8
ON / OFF Power Switch on PDB-4F
Circuit Breaker Models with Rated Output 1.42 Amps or below are Power
Limited
PDB-8F & PDB-8C are As configured in UL listed
products.
PDF-8F, & PDB-8C are UL listed Sub Assemblies As configured in
UL listed products
suitable for Access Control and Burglar alarm systems
All Input Terminal blocks and output terminal blocks on the PDB-8F module
are rated 40A with a wire range of 10 – 18AWG
Size: PDB-8F 3.87”H x 4.84”W x 1”D Mounting: 3.41”H x 4.49”W
Quality Manufactured in the USA
Custom Order details NOT UL LISTED
Specifications
Input Voltage ..................... 10.5 to 12.4vdc or 22.7 to 25.2vdc
Output Voltage ............................... virtually the same as Input
Current, Typical, with No Output Load .................... 90-160mA
Outputs 1–8 continuous duty each ......................... 1.23 Amps
Voltage Trigger .......................... 20% < Input min. 30vdc max.
Voltage Trigger isolation ............................................... Optical
EOL (End of Line) Trigger ...................... Trip +-50% of 2.2K Ω
Transfer Relay Contacts ............................................ 15Amps
Trouble Form C Contacts .................... 2A 120vac/1A 220vac
Triggered Form C Contacts .................. 2A 120vac/1A 220vac
UL Approvals
UL 294 – Access Control System Unit
UL 603 – Power supplies for Use with Burglar-Alarm Systems
ULC S318-96 – Power supplies for Burglar Alarm Systems
ULC S533-02 – Standard for Egress Door Securing and
Releasing Devices
PDB-8F-MMM-FFF
8 Fused Outputs with ATO Main/power pull fuse,
status LED’s and 1500 watt surge protector.
PDB-8C-MMM-CCC
8 PTC Circuit Breaker Outputs with ATO Main/power
pull fuse, status LED’s and 1500 watt surge protector.
FFF
Fuse Options
FFF = Fuse Rating in Amps (x.xx) standard 3agc Size:
(050 = 500ma); (100 = 1A); (200 = 2A);
(300 = 3A); (400 = 4A); (500 = 5A)
CCC
Circuit Breaker
options
CCC = PTC part number equaling the holding current
in Amps at UL rating 50C:
(090 = .7A); (135 = 1.04A); (160 = 1.23A);
(185 = 1.42A); (250 = 1.93A); (400 = 3.08A);
(500 = 3.85A); (600 = 4.62A)
MMM
Main Fuse options
MMM = Main Fuse Rating in Amps (xx.x) – Standard
Automotive ATO Size:
(050 = 5A); (075 = 7.5A); (100 = 10A);
(150 = 15A); (200 = 20A); (250 = 25A)
PDB-8F
PDB-8C
UL 294 – Access
Control System Unit
UL 603 – Power
Supplies for Use with
Burglar-Alarm
Systems
ULC S318-96 – Power
supplies for Burglar
Alarm Systems
ULC S533-02 –
Standard for Egress
Door Securing and
Releasing Devices