Installation Instructions
Battery Status
The section at the left of the middle section of
the screen shows the current battery status.
This section will only be enabled if a current
sensor is connected in line with the battery
for the Securitron AQL (See page 21).
Battery State of Charge
If enabled, a bar graph will display indicating the
estimated condition of the battery connected
to the supply. Once the battery is connected
and the Securitron Netlink detects current
flow, an Enable/Disable button will appear at
the bottom of the Battery Status area. If the
button is enabled, a four segment bar graph
display will appear with one end labeled "Full".
NOTE: It can take several minutes for an
accurate indication of battery condition.
The various possible states of the Battery
Condition bar graph display are as follows:
COLOR BARS BATTERY IS AT
4 Green Bars 80% to 100% charge
3 Green Bars 60% to 79% charge
2 Green Bars 40% to 59% charge
1 Green Bar 20% to 39% charge
1 Yellow Bar
6% to 19% charge
(email alert will be sent, if enabled)
1 Red Bar 5% or lower charge
When the battery discharges to one yellow bar,
an email alert will be sent if the Battery Condition
checkbox on the Reporting page is enabled.
• Status The Status field gives the state of the battery.
Possible states are “Charging”, “Charged”, or “Discharging”.
• Required Standby The required standby time as set
set in the Battery Settings section (See page 21).
• Actual Standby The measured battery standby time
as recorded during the Battery Test (See page 21).
• Replace Battery By This displays the scheduled
battery replacement date, which is calculated based
on the current date and the “Rated Battery Life” setting
entered on the Configure page. If the battery is within its
calculated life, the field will be green. Once the due date
has passed, this field will change to blue and an email
alert will be sent if enabled on the Reporting page.
• Enable/Disable Button This button will enable or
disable the Battery Status section. Disable the section
to prevent confusion and erroneous email alerts if the
current sensor is not connected in series with the battery.
Battery Enable /Disable Button (AQL main screen)
Battery Test Results
Battery Run Time
Test Warning