Installation Instructions
Setting up the Parameters for the Email Reports
The Securitron Netlink can send email alerts based on selectable conditions. If enabled, when the
selected conditions are met, the Securitron Netlink will send an email with an attached report file
(in CSV format). To set up the email alert conditions, click the Reporting link in the top menu.
Select the Email Alert Triggers
The “Alert Enable On” block of the Reporting page contains checkboxes for
the various conditions that can cause an email alert to be sent.
System Fault
If checked, a System Fault condition on a connected device will generate an email alert.
AC Fault
If checked, an AC fault condition on a connected device will generate an email alert.
Battery Backup Time
If checked, an alert will be generated if the required standby time
is not able to be met with the installed battery.
Current Sensor 1
If checked, a current outside the range set for Current Sensor 1 will generate an email alert.
External Temperature
If checked, an external temperature outside of the range set will generate an email alert.
Event1
If checked, a valid input on the Event1 Input will generate an email alert.
FAI Active
If checked, an active FAI Input on a connected device will cause an email alert.
Current Sensor 2
If checked, a current outside the range set for Current Sensor 2 will generate an email report.
Battery End of Life
If checked, an email alert will be sent when the Battery Runtime of the connected
device reaches the "Rated Battery Life" setting on the Configure page. When a
new battery is installed, the "Reset Timer for New Battery Installation" box on the
Programming page should be set to reset the Battery Runtime counter.
Battery Condition
An email alert will be sent when the battery charge is less than 20%
(one yellow bar on the "Bat. Condition" display on the power supply page).
ADC1 Reading
If checked, a voltage outside the range set for ADC1 will generate an email report.
Service Reminder
An email alert will be sent when the "Next Service Due" date
and time on the Configure page are reached.
Device Detect
An email alert will be sent when a device is connected or disconnected
from the Securitron Netlink board. This will notify the email recipient if the
Securitron Netlink loses communication with a connected device.
After setting the email alert triggers, click the Submit button at the bottom
of the “Alert Enable On” section for the settings to take effect.
30