Installation Instructions

3
Battery(s) average recharging
current
50 mA 75 mA 125 mA 250 mA
Battery(s) PTC self-resetting breaker 1A PTC 2A PTC 4A PTC 6A PTC
Model AQD1 AQD2 AQD4 AQD6
Battery(s) Reverse hookup
protection
Yes, 500 mA PTC Yes, 1A PTC Yes, 2A PTC Yes, 4A PTC
AQD Supervised Added Features
AC Status Output Relay 3Pin Terminal block
AC Fail “C” contacts rating <32VDC, <240VAC, 3A, resistive load only
Note: AC fail relay is a three position AC fail terminal block marked “NO, C, NC” are shown in the Normal, energized, AC ON condition.
Battery LED Indicator Red
Battery Max. Charge Voltage (no
load)
13.7 VDC /27.4 VDC
Battery Cutoff internal relay contacts
<32VDC, <240VAC, 3A, resistive load only
Low Battery Cutoff 9V / 18 V for 12 V / 24V setting
Note: Battery Cutoff Relay is normally energized for Fail-Safe operation.
Note: Sealed lead acid batteries have a typical life of 3 to 5 years. Make sure to mark batteries with the date they are installed.
Note: All power supplies are required to have a min of a 48 Hr recharge period to provide standby power of minimum 4 Hrs 15 Min of
alarm under full load conditions. Standby power has been evaluated in accordance with UL 1076 proprietary burglar alarm systems.
Physical
Module Dimensions 5.75" x 3.25" x 2.3" 4.88" x 3.75" x 2.06" 6.06" x 3.88" x 2.44" 7.36" x 4.04" x 1.75"
Note: Height Includes 7/16" standoffs, ½” standoffs minimum required
Module in Enclosure Dimensions 14" x 14" x 4.83"
Enclosure Weight 6.9 lbs
UL Approvals
UL 294 6th Edition
Listed
Listed
Listed
Line Security Level 1 1 1 1
Endurance Test Level 1 1 1 1
Attack test Level 1 1 1 1
Battery Standby Test Level 4 4 4 4
UL 603 Listed Listed Listed Listed
ULC-S318 Listed Listed Listed Listed
ULC-S533 Listed Listed Listed Listed
Compliance Notes:
Note 1: For UL294 Compliance when using 8 output PDB boards with fire trigger: Fire Alarm disconnect wire length must be less than
98.5 ft. (30m)
Note 2: For ULC-S318 compliance, the power supply battery fail line must be connected to and monitored by a control panel trouble
zone
Note 3: AQDX Series uses a standard power supply enclosure, not an attack proof enclosure. As such, they should not be used to power
a mercantile bell
Note 4: When using a battery that is not housed inside the power supply enclosure, the battery leads require protection from the
enclosure via the use of conduit. The enclosure shall be UL Listed to the above categories and shall have sufficient space to
accommodate the standby batteries.
Note 5: When using AQDXB modules in another enclosure, minimum standard spacing between live electrical circuits shall be taken
into account
Note 6: Model AQD1B power supply requires a low battery disconnect module (model# BDM) manufactured by Life Safety Power. This
device is required to provide the required battery disconnection for ULC-S318.
Note 7: Power supplies shall be installed in accordance with the National Electrical Code, ANSI/NFPA 70, Canadian Electrical Code, or any
other applicable codes
Maintenance
The power supply and standby batteries should be tested at least once a year as follows:
1. CHECK LEDs for normal state: AC ON Green, Trouble Normal ON Green (Amber LED indicates trouble), DC ON Red.