Installation Instructions
3 
Battery(s) average recharging 
current  
50 mA  75 mA  125 mA  250 mA 
Battery(s) PTC self-resetting breaker   1A PTC  2A PTC  4A PTC  6A PTC 
Model  AQD1  AQD2  AQD4  AQD6 
Battery(s) Reverse hookup 
protection  
Yes, 500 mA PTC  Yes, 1A PTC  Yes, 2A PTC  Yes, 4A PTC 
AQD Supervised Added Features 
AC Status Output Relay  3Pin Terminal block  
AC Fail “C” contacts rating   <32VDC, <240VAC, 3A, resistive load only 
Note: AC fail relay is a three position AC fail terminal block marked “NO, C, NC” are shown in the Normal, energized, AC ON condition. 
Battery LED Indicator   Red 
Battery Max. Charge Voltage (no 
load)  
13.7 VDC /27.4 VDC 
Battery Cutoff internal relay contacts 
<32VDC, <240VAC, 3A, resistive load only 
Low Battery Cutoff  9V / 18 V for 12 V / 24V setting 
Note: Battery Cutoff Relay is normally energized for Fail-Safe operation. 
Note: Sealed lead acid batteries have a typical life of 3 to 5 years. Make sure to mark batteries with the date they are installed. 
Note: All power supplies are required to have a min of a 48 Hr recharge period to provide standby power of minimum 4 Hrs 15 Min of 
alarm under full load conditions. Standby power has been evaluated in accordance with UL 1076 proprietary burglar alarm systems.  
Physical 
Module Dimensions  5.75" x 3.25" x 2.3"  4.88" x 3.75" x 2.06"  6.06" x 3.88" x 2.44"  7.36" x 4.04" x 1.75" 
Note: Height Includes 7/16" standoffs, ½” standoffs minimum required 
Module in Enclosure Dimensions  14" x 14" x 4.83" 
Enclosure Weight  6.9 lbs 
UL Approvals 
UL 294 6th Edition 
Listed 
Listed 
Listed 
Listed 
Line Security Level  1  1  1  1 
Endurance Test Level  1  1  1  1 
Attack test Level  1  1  1  1 
Battery Standby Test Level  4  4  4  4 
UL 603  Listed  Listed  Listed  Listed 
ULC-S318  Listed  Listed  Listed  Listed 
ULC-S533  Listed  Listed  Listed  Listed 
Compliance Notes:         
Note 1: For UL294 Compliance when using 8 output PDB boards with fire trigger: Fire Alarm disconnect wire length must be less than 
98.5 ft. (30m) 
Note 2: For ULC-S318 compliance, the power supply battery fail line must be connected to and monitored by a control panel trouble 
zone 
Note 3: AQDX Series uses a standard power supply enclosure, not an attack proof enclosure. As such, they should not be used to power 
a mercantile bell 
Note 4: When using a battery that is not housed inside the power supply enclosure, the battery leads require protection from the 
enclosure via the use of conduit. The enclosure shall be UL Listed to the above categories and shall have sufficient space to 
accommodate the standby batteries.  
Note 5: When using AQDXB modules in another enclosure, minimum standard spacing between live electrical circuits shall be taken 
into account 
Note 6: Model AQD1B power supply requires a low battery disconnect module (model# BDM) manufactured by Life Safety Power. This 
device is required to provide the required battery disconnection for ULC-S318.  
Note 7: Power supplies shall be installed in accordance with the National Electrical Code, ANSI/NFPA 70, Canadian Electrical Code, or any 
other applicable codes 
Maintenance 
The power supply and standby batteries should be tested at least once a year as follows: 
1.  CHECK LEDs for normal state: AC ON Green, Trouble Normal ON Green (Amber LED indicates trouble), DC ON Red. 