Technical data
8
Press the UP key rE1 will be displayed.
Listed are the codes and the menu they relate to in the parameter list
rE1 menu = coP = Compressor
rE2 menu = deF = Defrost
rE3 menu = Fan = Fans
rE4 menu = Luc = Light
rE5 menu = ALP = Temperature Alarms
rE6 menu = PP = Pressure Alarms
rE7 menu = ALP = Condensing Alarm
Use the up or the down key to scroll through the parameter labels.
When you have made the selection press the ENTER key to access the parameters.
Press the ENTER key to get to the next level.
Press the ENTER key to display the value and use the UP key or the DOWN key to change
the value.
Press the ENTER key to store the changes.
Use the UP or the DOWN key to scroll through the parameter labels.
Press the ENTER key to regain access to the code menu.
Press the ENTER key to confirm the changed value.
When all of the changes have been completed press the SET key 3 times to save the changes and return
to the menu.
Parameter Description for models with serial numbers ending A, B, C, D and E.
dro: Allows for the temperature to be displayed in either Celsius or Fahrenheit. 0 = °C. 1 = °F.
CA1: Calibration of Probe 1. Allows the value read by the probe to be adjusted up or down to suit site conditions.
Range –12°C to +12°C.
Compressor rE1 menu. coP
diF: differential. Allowable temperature rise between cut in and out of compressor. Range –12°C to +12°C.
HSE: Maximum set point. The maximum value that the set point can be adjusted in the operator functions.
Range from Lower set point to plus 150
LSE: Minimum set point. The minimum value that the set point can be adjusted in the operator functions.
Range from Maximum set point to minus 50.
dbi: Timed delay between 2 compressor start ups. (0 = no delay). Range in minutes 0 to 15.
dOF: Timed delay between compressor Off and next start (0 = no delay ). Range in minutes 0to 15.
Ont: Compressor run time in the event of room sensor failure. Range 0 to 250 minutes.
CFt: Compressor Off time in the event of room sensor failure. Range 0 to 250 minutes.
Defrost rE2 menu. dEF
dit: Timed interval between two subsequent defrost. Range 0 to 37 hours.
dEt: Timed defrost termination. Maximum timed duration of defrost even if termination temperature has not
been achieved. Range 1 to 250 minutes.
dCt: Defrost interval time count mode. Allows the setting of the defrost interval time against certain functions
(i.e. compressor run time = 0). Range 0 to 3.
0 = Compressor run time.
1 = Real time, interval of defrosts determined on a real time basis (i.e. with dit set for 4, defrost would occur
every 4 hours).
2 = Defrost occurs each time the compressor stops.
3 = Defrost occurs at set times using the real time clock.