Submittal Sheet

September 2011 DES.D.401.R1.02 1/2
FR7GH
Heat Pump Compressor
R134a
220-240V 50/60Hz
General
Code number 103G6683
Approvals EN 60335-2-34, UL984, CCC
Compressors on pallet 80
Application
Application HBP
Frequency Hz 50 60
Evaporating temperature °C -15 to 15 -15 to 15
Voltage range V 198 - 254 198 - 254
Max. condensing temperature continuous (short) °C 60 (70) 60 (70)
Max. winding temperature continuous (short) °C 125 (135) 125 (135)
Cooling requirements
Frequency Hz 50 60
Application
LBP MBP HBP LBP MBP HBP
32°C F
1
F
1
38°C F
1
F
1
43°C F
1
F
1
Remarks on application:
Motor
Motor type CSIR
LRA (rated after 4 sec. UL984), HST | LST A 9.1
Cut in Current, HST | LST A 9.1
Resistance, main | start winding (25°C) 8.8 12.0
Design
Displacement cm
3
6.93
Oil quantity (type) cm
3
450 (polyolester)
Maximum refrigerant charge g 900
Free gas volume in compressor cm
3
1350
Weight without electrical equipment kg 10.6
Dimensions
Height mm A 196
B 191
B1
B2
Suction connector location/I.D. mm | angle C 8.2 | 30°
material | comment Cu-plated steel | Al cap
Process connector location/I.D. mm | angle D 6.2 | 30°
material | comment Cu-plated steel | Al cap
Discharge connector location/I.D. mm | angle E 8.2 | 25°
material | comment Cu-plated steel | Al cap
Oil cooler connector location/I.D. mm | angle F
material | comment
Connector tolerance I.D. mm ±0.09
Remarks:
S =Staticcoolingnormallysufcient
O = Oil cooling
F
1
= Fan cooling 1.5 m/s
(compressor compartment temperature
equal to ambient temperature)
F
2
= Fan cooling 3.0 m/s necessary
SG =Suctiongascoolingnormallysufcent
= not applicable in this area

Summary of content (2 pages)