Unit installation
6
The Noble Air Ultraviolet Germicidal Lamp is designed for 9000-11,000 hours of continuous operation. After
9000 hours intensity of the lamp inside the duct diminishes and should be replaced. Even if the lamp is still
illuminated, replacement of the lamp is recommended by a qualified HVAC Service Technician.
• The installation should be done by a qualified
HVAC contractor.
1. Disconnect electrical service
2. Remove Noble Air cover.
3. Disconnect the lamp connector from the lamp
base.
4. Unscrew the nut for the lamp bracket and move or
remove the bracket from the lamp base. Remove
old lamp ( Be careful old lamp may still be hot ! ).
5. Replace the old lamp with the new lamp, making
sure the new lamp is clean. Remove fingerprints
and dirt with an alcohol wipe.
6. Place lamp bracket next to new lamp base and
secure with the nut.
7. Attach lamp connector to the lamp base.
8. Install the cover and screw tight to make sure the
interlock switch is activated.
9. Turn on electrical service.
UV lamps contain mercury like other household lamps and must be disposed of properly. State requirements and
recycling opportunities vary, go to www.lamprecycle.org for State Regulations & Contacts. Please contact
your county waste collection department for proper disposal details.
USE GLOVES AND EYE PROTECTION
If a lamp is broken, do not use a vacuum cleaner to pick up the waste . Instead, sweep up the waste into a plastic
bag and seal. Contact your county waste collection department for proper disposal details.
• 18 inch replacement lamp 6018…..1076-2Special
•
• 9 inch replacement lamp 6009……1068A-Special
•
• Ballast 6009,6018……….………..1651B
•
• Lamp Connector……………….…1014
•
• Interlock Switch………………….1047