Unit installation
6
The Second Wind Ultraviolet Germicidal Photo-catalytic Remote Lamp is designed for 9000-11,000 hours of con-
tinuous operation. After 9000 hours intensity of the lamp inside the duct diminishes and should be replaced. Even
if the lamp is still illuminated replacement of the lamp is recommended, by a qualified HVAC Service Techni-
cian.
• The installation should be done by a qualified
HVAC contractor.
1. Disconnect electrical service and turn unit off.
2. Remove screws from remote lamp connector.
3. Disconnect the lamp connector from the lamp
base.
4. Remove the screws from the RU lamp bracket and
remove old lamp ( Be careful old lamp may still be
hot ! ).
5. Replace the old lamp with the new lamp, making
sure the new lamp is clean. If the new lamp is dirty
or has fingerprints on it remove with an alcohol
wipe.
6. Place RU lamp bracket over new lamp base and
secure with the screws.
7. Attach lamp connector to the lamp base and use
screws to secure.
8. Turn on electrical service and unit.
UV lamps contain mercury like other household lamps and must be disposed of properly. State requirements and
recycling opportunities vary, go to www.lamprecycle.org for State Regulations & Contacts. Please contact
your county waste collection department for proper disposal details.
USE GLOVES AND EYE PROTECTION
If a lamp is broken, do not use a vacuum cleaner to pick up the waste . Instead, sweep up the waste into a plastic
bag and seal. Contact your county waste collection department for proper disposal details.
• 18 inch replacement lamp 1018RU or 1018-2RU 1076-2RSpecial
•
• 12 inch replacement lamp 1012RU or 1012-2RU 1083R-Special
•
• Ballast 1012RU,1012-2RU,1018RU,1018-2RU. 1651BR
•
• Lamp Connector RU Lamp Bracket
•
• Interlock Switch 1047