Unit installation
10
Second Wind Air Purification 1012RU/-2RU and
1018RU/-2RU units are mounted in the supply or
return to accommodate most HVAC systems. The
units install anywhere in the system to disinfect
molds, bacteria or reduce VOC contamination.
The housing is steel and comes in 2 sizes (12”
and 18” probes). All units are manufacturer
assembled and tested.
Models 1012RU/-2RU & 1018RU/-2RU:
The power source is a electronic, Class P, Sound
rated A, Type HL, NO PCB’s, type 1 outdoor
ballast meeting EMI requirements of CFR Title
47 Part 18 consumer. The operating range is from
120 VAC to 277 VAC and the current is
800ma@120vac. The ballast is designed to
operate at any airflow and relative humidity.
Second Wind lamps operate at 253.7 nm, ideal
for air disinfection, good for use at any velocities,
temperatures ranging from 30 - 170 F. Every
lamp has an extended lamp life coating which
helps maintain intensity levels at 85% even after
a year of operation. They are a High Output
(HO), T5 (15mm) diameter, lamp yielding 2/3
more output than standard lamps of the same
length. Base of the type “L” quartz glass is
ceramic, with triple-coiled electrodes made of
molybdendum lead in a clamped filament design.
Lamp connectors are 4-pin single ended circling
sockets. Lamp life shall not be less than 9000
hours.
Submitted device shall be tested under typical HVAC
conditions and in accordance with the general provisions of
IES Lighting Handbook, 1981 applications Volume. Total
output per one inch arc length shall be not less than 10uW/
cm2 at 1 meter in air of 45 F and 400 fpm
The titanium strips attached to the units are the
catalyst for the production of hydroxyl radicals in
the Photocatalytic process. They are made of
Titanium grade 2; 0.01% C, 0.005% N, 0.04%
Fe, 0.12% O, and balance Titanium. It has a
density of 4.5 g/cm cube, specific heat of 520 J/
kg K, electrical resistivity 50 micro ohms cm,
thermal expansion (10-6K) 9.1 (20-300C), tensile
strength 390 N/mm sq, and elongation A3 min
30%.
Dimensions:
Power Unit- 6”W x 8.5”L x 2.25” H
1012RU - 2-12” Remote Probes
1018RU - 2-18” Remote Probes
1012-2RU - 2-12” Remote Probes
1018-2RU - 2-18” Remote Probes
TiRU-Kit - Photo-Catalytic odor control upgrade kit.
Weight
1012RU– 9 lbs. 1018RU - 10 lbs.
1012-2RU– 9.5 lbs. 1018-2RU - 10.5 lbs.
Power Electronic Ballast
1012RU/TiRU: 120 VAC - 277 VAC
1018RU/TiRU: 120 VAC - 277 VAC
Lamps
18” 12”
Base Face in. - 17.2 12.0
Length mm - 436.0 303.0
Arc Length in.- 14.2 8.8
mm - 360 222
Current mA- 800 800
Wattage W- 40 25
Voltage @60Hz- 86 32
UV Output W- 10 5
UV Output @1M
uW/cm2 - 500 400
Lamp life hours- 9000 9000
Wiring
Number 18 teflon coated wire 600V, 105C.
URV Rating
Done at 400 fpm, 6” installation tracks, with TB Bacilli
rate constant with 60% reduction. Based on scale like
MERV rating Low- High, 1-15.
18” 12”
13 12
Warranty
Lifetime- Fixture, Ballast
1-Year Lamps