Instruction manual

5
1 Remove duct work in area you are going to
install the Second Wind unit. (Fig.4)
2 Remove the Second Wind Air Purifier from
carton and remove any wrapping that may
surround the lamp prior to lighting. Remove
front door and filter. Attach to installation area
of the duct with self tapping screws. (Fig.5)
3 Install new duct work to existing duct work
and 9000 series unit. (Fig.6-7).
4 Seal the seams with mastic or tape.
5 Reinstall the filter and the front cover of the
unit.
6 Plug the cord into a 110 volt outlet (Fig.8)
7 The air purifier is designed to remain on
continuously. (Fig.12) If lamp does not
illuminate, see the troubleshooting section.
Installation should be done by a qualified HVAC contractor.
Read all safety instructions at the beginning of this manual.
CAUTION: Equipment Damage Hazard. Ultraviolet light can cause color shift or surface
degradation and sometimes-structural degradation of non-metallic components. Select
mounting location that prevents exposure to plastic flexible duct components, polyurethane
foam insulation material, rubber hoses, wire insulation, etc. If mounting options are limited,
items should be protected with ultraviolet resistant material such as aluminum foil, alumi-
num duct tape, or metallic shields
1 Marker
2 Tinsnips
3 Drill
4 Drill Bits
5 5/16” &
11/32 “Nut
driver
6 Tape
Measure
7 Duct work