Certifications
(13)
SCHEDULE
(14)
to EU-Type Examination Certificate KEMA 02ATEX1248 X Issue No.5
Page 2/3
Form 227C
Version 1 (2016-04)
(15)
Description
The Magnetic Switches, Types MKF19X.AK / GKF19X.AK and MKR18X.AK / GKR18X.AK, are
used for contactless switching off resp. on of an electrical load by means of a movable magnet.
The enclosure of the magnetic switch is provided with an integral connection cable intended for
fixed installation.
The Magnetic Switches Types GKF19X.AK and GKR18X.AK are provided with a push button.
The push buttons are not assessed as a part of an Ex - enclosure according section 7 of standard
EN 60079-0.
Ambient temperature range MKF19X.AK / GKF19X.AK: -40 °C to +70 °C;
MKR18XSAK / GKR18XSAK: -25 °C to +60 °C;
MKR18XUAK / GKR18XUAK: -25 °C to +70 °C.
Electrical data
MKF19XSAK
GKF19XSAK
MKF19XUAK
MKF19XOAK
GKF19XUAK
GKF19XOAK
MKR18XSAK
GKR18XSAK
M
KR18XUAK
GKR18XUAK
Switching voltage
........
48 Vac/dc
30 Vac/dc
230
Vac/dc
230 Vac/dc
Switching current
........
max. 0,2 A
max. 0,2 A
max. 3
A
max. 1 A
Switching power
..........
10 W/VA
3 W/VA
60 W/VA
60 W/VA
Installation instructions
The instructions provided with the product shall be followed in detail to assure safe operation.
(16)
Report
Number
No. NL/KEM/ExTR08.0011/**.
(17)
S
pecific Conditions of Use
The Magnetic Switches shall be installed such, that danger of mechanical impact and exposure to
light is avoided.
The electrical specifications of the Magnetic Switches shall be met to secure the type of protection
Ex mb. If supplementary a non resetting device is used for protection of the switch or the circuit to
which the sensor is connected against overload, this device shall have a breaking capacity that is
in compliance with the prospective short circuit current of the power supply.
(18)
Essential Health and Safety Requirements
Covered by the standards listed at item (9).
(19)
Test documentation
As listed in Report No. NL/KEM/ExTR08.0011/**.