User's Manual
Programming the logger
49
Perform the following steps to configure the alarm thresholds:
Step
Description
1 In the segment Alarm Trigger – Settings specify whether there is a minimum
and / or a maximum threshold to be monitored by activating the respective
checkbox(es).
2
Enter the minimum and / or the maximum threshold into the respective field(s).
3
A hysteresis can be defined for alarm input preventing a constant triggering of the
alarm by measuring values fluctuating marginally around the threshold.
Enter a Hysteresis value. The Hysteresis value in percent designates a
symmetrical range around the specified threshold the input signal can fluctuate in
without having an impact on the current alarm status.
Example: (pressure sensor)
Min. level: 2.0 bar
Hysteresis: 10 %
The alarm does not switch on until the input signal reaches 90 %
of the specified threshold (here 1.8 bar). After this, the alarm does not
switch off until the input signal exceeds 110 % of the threshold
(here 2.2 bar).
Select a Debounce value. The input signal must cross the specified threshold not
only one time in order to switch an alarm on or off, but two times more after
specific periods of time. These periods of time, called ‘debounce’, always are a
multiple of the specified logging interval.
Example: (pressure sensor)
Logging interval: 5 sec
Min. level: 2.0 bar
Debounce: 15 sec
The alarm does not switch on until the input signal crosses the specified
threshold (2.0 bar) three times in succession (15 seconds).
4
Select the days of the week alarming should be active on by marking the
respective checkbox(es).
Configuring
alarm trigger