User's Manual
Programming the logger
46
6.2.1.3 Input type examples
A 10 bar pressure sensor with voltage output is connected to a channel of the logger.
Input type:
Unit:
Voltage 0-5V
bar
The lower limit of the measuring range (0 bar) is indicated by a voltage value of 0 V
while the upper limit (10 bar) correlates with 5 V. As a result, the fields must be
populated as follows:
NOTE
The maximum permissable input voltage is 5 V.
A level meter with frequency output is installed in a 430 l tank.
Input type:
Unit:
Frequency
l
The maximum level of 430 l is indicated by a frequency of 6000 Hz. As a result, the
fields must be populated as follows:
The maximum permissable frequency is 6000 Hz. If the connected sensor
transmits higher frequencies, a frequency divider must be interconnected.
Input type Voltage
Input type Frequency