User guide

www.honeywell.com/security
144 | Performance Series HQA Digital Video Recorder User Guide
Guidelines for Connecting Alarm Input Ports
Ground alarm inputs. Choose from normally open (NO) or normally closed (NC).
Connect the COM end and GND end of the alarm detector in parallel. Supply external
power to the alarm detector.
Connect the ground of the DVR and the ground of the alarm detector in parallel.
Connect the NC port of the alarm sensor to the DVR alarm input.
Use the same ground as the DVR if you are supplying external power to the alarm device.
Guidelines for Connecting Alarm Output Ports
Provide external power to external alarm device.
To prevent overloading, carefully review the following relay specifications:
Material
Nickel/silver contacts with gold plating
Rating (Resistance
Load)
Rated switch capacity 30 V DC 2A; 125 V AC 1A
Maximum switch power 125 V A, 160 W
Maximum switch voltage 250 V AC; 220 V DC
Maximum switch currency 1 A
Insulation
Between touches with same polarity 1000 V AC/1 minute
Between touches with different polarity 1000 V AC/1 minute
Between touch and winding 1000 V AC/1 minute
Surge voltage
Between touches with same polarity 1500 V (10 × 160 us)
Length of open time
3 ms maximum
Length of closed time
3 ms maximum
Longevity
Mechanical 50 ×106 times (3 Hz)
Electrical 200 × 1030 times (0.5 Hz)
Temperature
–40°F to 158°F (–40°C to 70°C)