Specifications
RN: 3-17
RS3: Software Release Notes for P1 R4.2
System Improvements
Table 3.7. RS3 Corrected Software Discrepancies in Previous P1 Releases (continued)
ID
Fixed in
Release
NumberDescription
Controller
803394
Logic prolog ramp() malfunction with multiple ramp function on a single step.
Fixed.
1.2
Controller
803401
When using a PLC write Mask other than FFFF, the PLC controller is turning
on bits other than those turned on in the source link.
Fixed.
1.2
Controller
803781
The HART Output Block (HOB) default values for Dead Time and Deviation
Alarm are set to 0 at startup, which is incorrect.
Fixed.
1.2
Controller
803815
If the HART address of a transmitter attached to a FIM is made non--zero
from the RS3 console, HART communications stop.
Fixed.
3.1
Controller
803826
Only 7 bytes are allocated for the additional status provided by HART
command 48. As many as 25 can be provided, leading to overwriting data.
Fixed.
1.2
Controller
803924
RS3 output block went to backtracking mode when Fieldvue valve reported
a deviation alert.
Fixed.
1.2
Controller
803925
RS3 interrupts a HART 275 when it is trying to calibrate a Fieldvue valve.
Control mode gets changed to RSP.
Fixed.
1.2
Controller
803926
Inadvertent download of default values to a Fieldvue valve causes the valve
to go out of service.
Fixed.
1.2
Controller
803961
If the primary controller is shut off and left in the Card Cage, communica-
tions to one or both ports to the PLC can be lost.
Fixed.
3.1
Controller
804053
If AMS is attempting to communicate with a device via RS3 pass through,
and any block on the FIC or FIM is configured without a device attached,
AMS has difficulty communicating with any other device on that particular
FIC or FIM.
Fixed.
1.3
Controller
804065
If a FIC or FIM has a non-smart analog device attached, AMS attempts to
scan or communicate with smart devices on that FIC or FIM, and is unable
to see many of them.
Fixed.
1.3
Controller
804366
Under a number of observed circumstances, digital comm can be lost for 1
or more SIBs on a particular FIM.
Fixed.
1.4