Specifications
RN: 3-16
RS3: Software Release Notes for P1 R4.2
System Improvements
Table 3.7. RS3 Corrected Software Discrepancies in Previous P1 Releases (continued)
ID
Fixed in
Release
NumberDescription
Controller
801426
RS3 V18R2.3 cannot support some PLCs because RS3 asks for more coils
than are configured in the PLC.
Fixed.
1.0
Controller
801471
On HOB, when the HOB is switching back from digital to analog, the valve
display does not automatically show the right control mode.
Fixed.
1.0
Controller
801849
An upload of the information in a smart output device cannot be completed.
Fixed.
1.0
Controller
802489
If an RS3 Operator Station is displaying a continuous link with a value of 0,
and that link is unconfigured in the RS3 Command Console, the
unconfigured link is still recognized as “normal” by the RS3 Operator
Station.
Fixed.
1.1
Controller
803041
If an HOB block gets an error on an MAO FIM, the tracking value passed to
the block driving the HOB will be in error. Recovery will not be smooth.
Fixed.
1.1
Controller
803047
Customer with HOBs configured by V18 software who is updating to fix the
wrong variable problem in PCR 801380 must delete HOBS and reconfigure.
Fixed.
1.1
Controller
803084
HOB tracking is invoked if HART communications are lost even though the
rest of the loop is intact.
Fixed.
1.1
Controller
800762
For a PLC+ on an MPC II with two ports configured, ModBus protocol, and
RTU format, update time might slow significantly if one PLC is shut off.
Fixed.
1.2
Controller
801691
Some smart I/O communication errors intermittently caused controller
crashes.
Fixed.
1.2
Controller
801732
When subscribed to a register and the register is unconfigured, no
notification is sent from the RNI and the RS3 Operator Station View screen
remains unchanged.
Fixed.
1.2
Controller
802874
Function time(6) 4-digit display of YEAR shows 1900 instead of 2000 in
block_step_logic or Batch.
Fixed.
1.2
Controller
803376
When a smart output device reports a deviation alarm, the screens display a
deviation alarm, but the block is not in alarm.
Fixed.
1.2