Table 3.7. RS3 Corrected Software Discrepancies in Previous P1 Releases (continued)
ID
Fixed in
Release
NumberDescription
Console
803914
On 68040 consoles, the bars and symbols on group displays and tuning
displays start to disappear pixel by pixel.
Fixed.
1.2
Console
804165
If you enter a date later than 2000 into an SIB or HOB Date field, “0000” is
actually sent to the device and is displayed incorrectly in AMS. AMS
displays 01/01/2000 as 00/00/00
Fixed.
2.0
Console
804905
Block operations from graphics are intermittently ignored.
Fixed.
3.2
Controller
800542
When disabled and enabled, a controller might become stuck in standby
mode when it comes back up.
Fixed.
1.0
Controller
800573
In a ControlBlock, the ssm (seconds since midnight) time function can alter
the values of subsequent time functions.
Fixed.
1.0
Controller
800679
There is no error message when an SIB or VIB block is loaded to another
card in the cage and the SIB or HOB tag field has an incorrect address.
Fixed.
1.0
Controller
801113
If you change an HOB from digital to analog, you must execute the “Update
xmtr variables” command to implement the change.
Fixed.
1.0
Controller
801360
CB documentation omission: when controllers switch, the data valid flag
changes to 0 for one scan cycle of the controller processor.
Fixed.
1.0
Controller
801381
The HOB device status displays the the valve serial number instead of the
final assembly number . Some users would prefer to see the assembly
number .
Fixed.
1.0
Controller
801382
RS3 does not allow the Fieldvue secondary master to communicate with the
RS3.
Fixed.
1.0
Controller
801387
System flags for block inputs A through O are interpreted as user flags.
Fixed.
1.0
Controller
801388
A secondary master device may not be able to calibrate a smart output field
device if the RS3 changes the HOB mode during an upload.
Fixed.
1.0
Controller
801411
If an AOB, AIB, SIB, or HOB is configured with no IO hardware on a point
greater than 8, a bad block alarm is generated, making the block useless.
Fixed.
1.0