RS3: Software Release Notes for P1 R4.2
System Improvements
Table 3.7. RS3 Corrected Software Discrepancies in Previous P1 Releases (continued)
ID
Fixed in
Release
NumberDescription
Console
801323
Console crashed during printing of a report. No alarms appeared.
Fixed.
1.0
Console
801362
If more than 32 consoles and SRUs are on linked PeerWays, a console
might not be able to access a process graphic on a different node.
Fixed.
1.0
Console
801375
One task undoes what another task had done so changes are not made.
Fixed
1.0
Console
801376
Task neglected to restore rrow variable to its original value of zero, causing
crash dumps.
Fixed.
1.0
Console
801417
The console may crash if you press the arrow key on the numeric key pad
and move the trackball at the same time.
Fixed.
1.0
Console
801469
Problem with graphic in V17 AND V18 R2.1 French console: Duplicating
portion of graphic to another location reboots the console.
Fixed.
1.0
Console
801615
The loop power module status bits on the field IO status screen for MAIO
are displayed in the alarm color whenever they are 1, even if meaningless.
Fixed.
1.0
Console
802976
Console can be made to crash when using “Disk Virtual Controller” opera-
tion.
Fixed.
3.1
Console
803245
Because the disk configure function on the SMS was under the impression
that reports were still active on the SMS, it refused to proceed.
Fixed.
1.2
Console
152623
If the alarm log is not enabled or not defined, a large number of “Illegal
Volume/File Name Used” alarms are generated.
Fixed.
1.2
Console
152648
The memory dump diagnostic operation does not save the address of
overlays to disk.
Fixed.
1.2
Console
802622
An operator can change the output option field on the HOB block config
screen. This should be limited to a configuror .
Fixed.
1.2
Console
803091
The console crashes when a large negative number is entered in the output
of the SIB block.
Fixed.
1.2