Specifications

RN: 3-13
RS3: Software Release Notes for P1 R4.2
System Improvements
Table 3.7. RS3 Corrected Software Discrepancies in Previous P1 Releases (continued)
ID
Fixed in
Release
NumberDescription
Console
152786
When viewing the Disk Directory Peerway screen, all drives are listed under
the drive 1 position for several seconds.
Fixed.
1.0
Console
152821
When configuring a console with a blank disk, the default size of the
Console Program Folder is too small to boot the console software.
Fixed.
1.0
Console
800182
Alarm Log Display screen crashes the console if 10--11 nodes are entered
on the find, filter, and sort criteria areas
Fixed.
3.1
Console
800672
Variables of 10 or more characters from SIB or VIB I/O block might cause
the console to crash when a report is generated.
Fixed.
1.0
Console
800804
Items defined in event list configuration are not readable when printed from
a 68040 console. They print correctly from a 68020 console.
Fixed.
1.0
Console
800976
If a block descriptor uses all 24 characters, the BLKDES graphic object
does not display the descriptor.
Fixed.
1.0
Console
801076
When creating a boot tape, the default New Volume Name” can confuse
Batch.
Fixed.
1.0
Console
801107
Process graphics with complex layering of windows might crash during
periods of high alarm activity.
Fixed.
1.0
Console
801187
When the Operator” is specified as the “Key Class for Reports on the Con-
sole Configuration screen, the operator can delete batch scripts.
Fixed.
3.1
Console
801226
On the Report Config Directory screen, the autoprint status is displayed as
a garbage character instead of a “Y” or “N”.
Fixed.
1.0
Console
801242
Russian consoles only: the SIB block alarms display garbage characters.
Fixed.
1.0
Console
801260
When a graphic is upgraded from V15R5 to V18R2.2, link objects for
discrete registers (for example, =1A--10/a) no longer animate in V18.
Fixed.
1.0
Console
801310
On the 68040 console, block descriptors with 24 or more characters cause
the console to crash.
Fixed.
1.0
(continued on next page)