Specifications

RN: 3-12
RS3: Software Release Notes for P1 R4.2
System Improvements
Table 3.7. RS3 Corrected Software Discrepancies in Previous P1 Releases (continued)
ID
Fixed in
Release
NumberDescription
Batch
804551
Checksum is incorrectly calculated after a script is saved (ctrl--w).
NOTE: The following information is applicable only to ABC Batch users who
use the Validation “HALT” or “W ARN” in any of the Batch Unit, Material or
Operation Tables:
In software versions V18 through P1 R2.0, in ABC Recipe scripts where you
changed the symbol table (added or deleted shared or local variables) in the
script, and then wrote the script out once (a single CTL--W), the checksum
that is recorded with the script on the RBL File list may not be correct. This
checksum is read into the Tables and used for recipe validation. In some
cases, if you re-wrote t he script (a second CT L--W ), the script checksum
may change, providing a different checksum. The different checksum could
affect your recipes (HALT or WARN) if you re-wrote the scripts at different
times.
This has been fixed. Now, the first write of the script (CTL--W) will always
give you the correct checksum. Any subsequent writes to the same script
will not change the checksum. However, you may have some existing
scripts that do not have the correct checksum.
In order to verify that you have all the correct checksum values, you must
write out all of your RBL scripts from a console updated to P1 R3.2
software. If the checksum for any of the scripts changes when you write
them out (CTL--W), you must update the Batch Unit Table, Batch Material
Table, and Batch Operation Table script checksum values for these scripts.
3.1
Batch
804673
If you write BAMT to ASCII and back to table, reports unsuccessful”, and
deletes both the Primary and the Backup files from disk.
Fixed.
3.1
Comm
800256
Error in V18 PeerWay Interface Manual for field codes 5 & 6, page 1--4--7:
SCI cannot write to the block mode and output of I/O blocks. SCI can only
write to the block mode and output of ControlBlocks.
Fixed.
1.0
Comm
800356
SCI cannot read field codes higher than 1500.
Fixed.
1.0
Comm
800857
On the SCI, saving the configuration and sending a message pair in quick
succession might disable data transmission.
Fixed.
1.0
Console
102845
In the tuning display operation, changing the scaling at the left of the
faceplate does not change the alarm limit indication.
Fixed.
1.0
Console
150430
If you join objects and try to grab one object and MOVE off screen to the
left, the console may crash.
Fixed.
3.1
Console
152623
If the alarm log is not enabled or not defined, a large number of “Illegal
Volume/File Name Used” alarms are generated.
Fixed.
1.0
(continued on next page)