Specifications
RN: 3-5
RS3: Software Release Notes for P1 R4.2
System Improvements
Table 3.6. RS3 Corrected Software Discrepancies in P1, Release 3.2 (continued)
ID RatingDescription
Batch
805157
Some V17 ABC recipes do not upgrade, had to manually change header to get
recipe to upgrade to P1 R3.2.
Fixed
D4
Batch
805513
Recipes won’t update in some cases unless there is at least one parameter in the
Batch Operations Table
Fixed
D4
Batch
805556
Console allows manually assigning same BAPU to two different recipes.
Fixed
D4
CP
804964
If CF is changed from P1 R3 to V18 (or earlier P1), NV mem will stop backing up.
Fixed
D4
Console
101302
Unexpected results from enabling the “Op Chg” field on the Console Configuration
Screen
Fixed
D3
Console
801118
When multiple reports are imbedded in another report (on the Report Generation
screen), reports might not be displayed.
Fixed
D3
Console
803561
Cyrillic consoles (P1 and V18) show only the first 8 characters (of a total of 16) of
a PLCB’s Flag Name field.
Fixed
D3
Console
803725
Saving the CAB for the ControlFile only works once or twice. After that saving
from any console on the PeerWay gives a Controller Got Bad Message.
Fixed
D3
Console
803765
Tic Master cannot spread the slot width from the PeerWa y Node screen.
Fixed
D3
Console
804933
Block Out on scaled PLC blocks is in Green, instead of in red, like normal outputs.
Fixed
D3
Console
805081
The screen title ”FIC Detail” should be changed to ”Field I/O Detail” When FIMs
were developed the FIC status screen was changed to Field I/O, missed
Fixed
D3
Console
101699
Batch monitor screen does not show the correct backup volume name
Fixed
D4
Console
150871
Generating a report from a node that does not exist in another report crashes the
console
Fixed
D4
Console
801127
The block print utility can crash the console when the printer is offline.
Fixed
D4
(continued on next page)