Specifications
RN: 3-2
RS3: Software Release Notes for P1 R4.2
System Improvements
Table 3.2. RS3 Corrected Software Discrepancies in P1, Release 4.1
ID
Description Rating
Controller
0469
During a controller start or redundancy switchover, Multipoint Input values may mo-
mentarily be read at the value of zero or the low cutoff value, generating process or
hardware low value alarms. This condition will only exist for several seconds and
the Hold Forward flag will be set t o on. This HF flag can be used to detect t he sys-
tem error vs. the actual alarm condition.
Fixed
A1
Table 3.3. RS3 Corrected Software Discrepancies in P1, Release 4.0
ID
Description Rating
Batch
805217
0168
The “Batch ID” source field for a recipe started with runrecipe, now indicates
started by System instead of by Operator.
Fixed
D4
Batch
801407
Batch Material Tables now correctly maintain High and Low limits on all properties
when upgraded from V18 versions.
Fixed
D3
Batch
800941
The Tape Descriptor is displayed on tape directory for the console when the tape is
loaded.
Fixed
D3
Batch
0255
Corrected case on Batch Working recipe where user could leave a parameter as
“No Value” and system would inadvertently unlock the wrong recipe unit.
Fixed
D4
Batch
805390
If a working recipe is killed while in static mode, the ABC log file is changed to a
finished recipe rather than being left as a working recipe,
Fixed
D4
Batch
805376/123
Corrected Material Table ASCII conversion when material type “RAW” is used.
Fixed
D4
Batch
805482/126
If a Batch Control Recipe start is aborted, the working recipe is no longer created.
Fixed
D4
Batch
805554/150
The Autodelete function is now called when the user attempts to edit an ABC Batch
Working recipe, (no longer see the error “Could not create ~file).
Fixed
D4
Batch
805259/167
SMS console now allows printing scripts from the RBL File screen.
Fixed
D3
Console
805081
The screen title “FIC Detail” was changed to “Field I/O Detail”.
Fixed
D3
Console
804552
Graphic objects linked to an icon object now correctly shows the condition color
change when the graphic is first displayed.
Fixed
D4
Console
805539/116
Report objects can now be selected properly on Report Configuration screens.
Fixed
D2
Console
805441/112
“M ON” DISC on a graphic correctly animates when the operator presses enter.
Fixed
D4
(continued on next page)