Specifications

RN: 2-37
RS3: Software Release Notes for P1 R4.2
Software and Hardware Requirements
P1 R4.1 Software Image Versions
Table 2.38. P1 R4.1 Software Image Versions
Image
Version Image Version
$MPC2+_P1 (see Note 1)
P1.18
$MPC5_P1 (see Note 1)
P1.18
Note 1
This RS3 Base Software release is identical to P1 R4.0 except that T rack issue #0469 has now been
corrected. Only two images on the tape have changed, $MPC2+_P1 and $MPC5_P1.
Emerson Process Management has issued a safety notice dated April 24, 2001, for this Release.
(See KBA #AUS1--247--010419112733).
For the images identified, a discrepancy has been identified as Track Issue #0535. The T rack Issue #0535
deals with the following: The analog input values from the MultiPoint Analog Input (MAI) FIM connected to
the Controller (MPC2 or MPC5) stops updating without any indication or alarm to the operator. This WILL
occur when the MPC2 or MPC5 Controller(simplex or redundant) is loaded with image software version
P1.18 and connected to any MAI FIM. The ’Hold Forward’ (HF) flag, after 124.25 days of uninterrupted
runtime, will be set and prevent the actual analog value from being used.
(See KBA# AUS1--247--010419112733 for additional information on this issue.)
P1 R4.2 Software Image Versions
Table 2.39. P1 R4.2 Software Image Versions
Image
Version Image Version
$MPC2+_P1 (see Note 1)
P1.19
$MPC5_P1 (see Note 1)
P1.19
Note 1
This is a mandatory upgrade for Customers currently running systems with base software P1 R4.1. For all
other Customers this is information only.
This RS3 Base Software release is identical to P1 R4.1 except that T rack issue #0535 has now been