Specifications

RN: 2-36
RS3: Software Release Notes for P1 R4.2
Software and Hardware Requirements
P1 R4.0 Software Image Versions
Table 2.37. P1 R4.0 Software Image Versions
Image
Version Image Version
ECCBOOT (English)
P1.30
$$MPCAS18
18.11
ECCBOOT (French)
P1.31
$$MPCAP18
18.11
ECCBOOT (German)
P1.32
$$MPCAT18
18.11
ECCBOOT (Russian)
P1.29
$$MPTUN18
18.11
SMSBOOT (English)
P1.30
$$PLCM18
18.10
SMSBOOT (French)
P1.31
$$SMART18
18.10
SMSBOOT (German)
P1.32
$$STDC_18
18.11
SMSBOOT (Russian)
P1.29
$MPC2+_18
18.11
$CP4_P1
P1.15
$RBLC2_18
18.10
$CP4BA_P1
P1.15
$$AFIC1_6
1.6
$CP5_P1
P1.15
$$AFIC4_8
4.8
$CP5BA_P1
P1.15
$$TFIC3_1
3.1
$RBLC2_P1
P1.17
$$DIO3_4 (DIO1)
3.4
$MPC2+_P1 (see Note 1)
P1.17
$$DLH4_0 (DIO2)
4.0
$RBLC5_P1
P1.17
$$MAIO3_3
3.3
$MPC5_P1 (see Note 1)
P1.17
$$HIAPROG
11.22
$CP4_18
18.14
$$SCIPROG
P1.02
$$CPMAX18
18.15
Process Graphics
18.01
$$MPCA18
18.11
Process Symbols
18.01
Note 1:
For the images identified, a discrepancy has been identified as Track Issue #0469. The Track Issue #0469
deals with the following: During a controller start or redundancy switchover, MultiPoint Input values may
momentarily be read at the value of zero or the low cutoff value, generating process or hardware low value
alarms. This condition will only exist for several seconds and the Hold Forward flag (HF) will be set to on.
This HF flag can be used to detect the system error vs. the actual alarm condition.
(See KBA #AUS1--208--000824144155 for additional information on this issue.)