Specifications

RN: 2-3
RS3: Software Release Notes for P1 R4.2
Software and Hardware Requirements
Table 2.1. Supported PeerW ay Node Hardware Combinations for P1 PeerWay Image Designation
Consoles
ControlFiles
(1)
Future
DeltaV
Operate
for RS3
ROS MTCC
or
SMS
Coordinator
Processors
Memory Controllers Consult Tables
for Boot ROM
and Images
Yes ROS 4.0.1
with SP 1
68040
CP5 4MBNV
RAM
MPC5 Table 2.14 or
Table 2.15,
and
Table 2.22
CP5 4MBNV
RAM
MPC5
MPCII
Table 2.16 or
Table 2.17,
and
Table 2.22
CPIV+ or
CPIV
4MBNV
RAM
MPC5 Table 2.18 or
Table 2.19,
and
Table 2.22
CPIV+ or
CPIV
4MBNV
RAM or
2MBNV
RAM
MPCII Table 2.20 or
Table 2.21
and
Table 2.29
(1)
P1 Images only. Consult Table 2.14 to Table 2.22.
Notes:
D
Other acceptable nodes not shown are HIA, SCI, RNI, VAX, and TRU. Consult Table 2.31 and Table 2.32.
As shown in Table 2.1 above, in order to have a P1 PeerWay Image
Designation with P1 R4.x software release:
D
Any CPI’s or CPII’s used with earlier releases of software will
have to be upgraded to a minimum of CPIV, or to a minimum of
CP5 if MPCII and MPC5 are to be combined within a ControlFile.
D
Any Memory cards less than the 2 MB NV will also have to be
upgraded to a m inimum of 2 MB NV, or to a minimum of 4 M B NV
if MPC5 controllers are to be used within the same ControlFile.
D
Any controllers earlier than an MPCII will also be required to be
updated to a m inimum of MPCII.
The P1 R4.x software r elease with a P1 PeerWay Image Designation
supports the latest:
D
Coordinator Processor 5 (CP5)
D
RS3 Operator Station (ROS) Version 4.x or higher.
D
RS3 Network Interface (RNI) Version 4.x or higher,
D
HIA, SCI, VAX, and TRU
D
Future product DeltaV Operate for RS3