Specifications
RN: 5-97
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
Description: The new part number for the MAIO16 FIM was added on
page 7-3-2.
D
MAIO16 Field Interface Module (FIM):
4--20 mA Output 16 Point 10P54080004 or
10P58080005
Description: The new part number for the MAI32 FIM was added on
page 7-3-27.
D
MAI32 Field Interface M odule (FIM) 10P53190004 or
10P58300005
Description: Information on the new MAI32 F IM was added to Table
7.3.11 on page 7-3-38.
Table 7.3.11. MAI32 Termination Panel Jumpers
Jumper
Position Effect
HDL01--HDL
16
H
D
R
0
1
H
D
R
Full left
System-powered input point
H
D
R
01--
H
D
R
16
Point Type
Full right
Self-powered input point
One jumper
A--C at 1--2
Cage address for Left Group of points
L01--L16 (A is recommended)
HD33
ADDRESS
One jumper
B--D at 1--2
Cage address for Right Group of points
R01--R16 (B is recommended)
Pat1--2
Required for correct parity*
HD34
L
O
O
P
P
W
R
ENABLE
Enables detection of loop power loss
L
O
O
PPWR
DETECT
DISABLE
Disables detection of loop power loss
SH and CH
connected
All field wiring shields are connected to panel
chassis ground
TB21
Shield
SH and CH
open
All field wiring shields are connected together
and are floating with respect to panel chassis
ground
S
h
i
e
l
d
Grounding
SH
connected to
external
ground
All field wiring shields are connected together
and are connected to the external ground
point
* Not required for MAI32 FIM 10P58300005.