Specifications
RN: 5-87
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
Site Preparation and Installation Manual Changes
Changes to the Site Preparation and Installation Manual (SP) are a
result of additional information concerning:
D
Introduction of a new MAI32 F IM with the P1 R3.4 release
D
FIM replacement and redundancy
D
MAI32 termination panel jumpers
D
Power supply redundancy
The following information describes the changes to this manual.
SP: Chapter 1 (Preliminary Planning)
SP-1: Section 2 (Power Requirements)
Description: A new paragraph was added to the bottom of page 1-2-7
under the heading “AC Power” to include more information on System
Power Supply Units.
System Power Supply Units are switching power supplies that normally
do not require any additional line conditioning. These power supply
units are regulated to a nominal 26 VDC. Each unit has the mains
supply terminations built directly into its housing. See Section 1-4 in the
Service Manual for additional specifications of the System Power
Supply Unit.
Description: The second item on page 1-2-9 under the heading “AC
Power Consumption” was modified to include power supply modules.
2. Finding the number of AC/DC power supplies or the number of
power supply modules, whichever is applicable.
Description: An addition to Table 1.2.1 on page 1-2 -11 was made to
show information on the MAI 32-point Input Termination Panel with FIM
10P58300005.
Component
Nominal
Current
at 30 VDC
Amps
Nominal
Current
at 24 VDC
Amps
Heat
Output
Watts
(BTU/hr)
Consoles and PeerWay Interfaces
MAI 32-point Input Termination Panel (10P5349xxxx) with
FIM 10P58300005
.10 .11
5
(17)