Specifications

RN: 5-82
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
Description: Information on Analog FIM Bits for bits 0, 1, and 2 was
changed on page 10-5-15.
Table 10.5.8. FIC/FIM Status Bits
Status
for:
Status
Bits
Bit Description
Analog
FIM
Bits:
xxxx
x1xx
2
MAI16 and MAO16:
Loop Power Module status bits: 0 for Loop Power Module A.
1 for Loop Power Module B.
MAI32:
Not used.
xxxx
xx1x
1
Set to 0 when the Loop Power is good.
Set to 1 when the Loop Power is bad.
xxxx
xxx1
0
MAI16 and MAO16:
Set to 0 when the Loop Power Module is present.
Set to 1 when the Loop Power Module is absent.
MAI32:
Set to 0 when the Loop Power Detect jumper is in the ENABLE
position.
Set to 1 when the Loop Power Detect jumper is in the DISABLE
position.
Description: Changes to pages 10-5-18 and 10-5-19 are result of a
change in the name of a detail screen. The name changed from “FIC
Detail” to Field I/O Detail”.
Field I/O Detail Screen (FIC Detail Screen)
The FIeld I/O Detail screen (previously the FIC Detail screen) displays
information about the blocks that are associated with an individual FIC
or FIM. This screen is for display purposes only. To call up the Field I/O
Detail screen, cursor to the desired FIC or FIM and press [SELECT]
from the Field I/O Status screen (previously the FIC Status screen).
To view the F ield I/O Detail screen for a F IC or FIM, cursor to the
desired card and press [SELECT]. If any I/O Block is in alarm, the
associated F IC or FIM will be in a corresponding color.
Figure 10.5.2 shows the Field I/O Detail screen. Table 10.5.9 describes
the Field I/O Detail screen fields.