Specifications
RN: 5-81
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
Description: Additional information was added to the Node field
description and a Refresh Rate field was added to Table 10.3.3. on
page 10-3-18 to reflect changes made to the Memory View screen.
Table 10.3.3. Memory View Screen Field Description
Field
Description
Node
Specifies the node number of the source of the memory data for the primary
CP or the Controller Processors in slots A--H.
For example:
When Node 136 is entered, the memory of the primary CP for Node 136
is read.
When Node =136A is entered, the memory of the Controller Processor in
slot A of Node 136 is read.
NOTE: With a redundant pair of controllers, only the memory of the
primary Controller Processor can be read.
Refresh
Rate
Specifies the amount of time that the information will be updated. A specific
value or “never” can be entered.
SV-10: Section 5 (Troubleshooting Input/Output)
Description: The first paragraph on page 10-5-2 was changed to
reflect the new name for the status screen. The name changed from
“FIC Status” to “Field I/O Status”.
When a primary Field Interface Card (FIC) with redundancy fails, the
redundant F IC takes over. T he failed FIC lights its red LED or flashes its
green LED. Replace the failed FIC and determine that the new FIC has
its green LED lighted and that the F ield I/O Status screen (previously
the FIC Status screen) shows no error for the F IC. The “Health” field of
the pr imary FI C will still show “Bad”.