Specifications
RN: 5-79
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
One M AIO Termination Panel (1984--4383--0002) and an MAIO FIM can
support up to16 points on 8 dual-channel barriers. Use an MAIO Input
FIM (10P54040004 or 10P57700005) for inputs or an MAIO Output FIM
(10P54080004 or 10P58080005) for outputs. Use Marshaling Panel
Cable 1984--4298--xxxx.
Description: The part number for the new MAO Output F IM was added
to page 6-6-25.
Two FIMs are available:
D
MAI16 4--20 mA Input 10P54040004 or
10P57700005
D
MAO16 4 --20 mA Output 10P54080004 or
10P58080005
SV: Chapter 8 (Calibration)
SV-8: Section 1 (Calibrating Serial I/O Field Interface
Cards)
Description: The first part number in the third row of Table 8.1.1 on
page 8-1-1 was corrected. The part number was changed from
10P54440002 to 10P57240002.
Table 8.1.1. Serial I/O Field Interface Cards
FIC
Characteristics
1984--2480--000x Two input/one output (4--20 mA) FIC, no redundancy
10P59150002
or
10P54440002
or
1984--2518--000x
T wo input/one output (4--20 mA) FIC, redundancy
10P59270002
or
10P57240002
or
1984--2519--000x
Assembly:
T wo input/one output (4--20 mA) FIC, redundancy
combined with
Smart Transmitter Interface Daughterboard (P/N
10P5450000x)
SV-8: Section 6 (Calibrating Multipoint Analog I/O (MAIO)
Output and Input Points)
Description: Step 1 on page 8-6 -5 was modified to read as follows.
1. Remove the r edundant Field Interface Module (F IM) from service
by unplugging it (if a redundant F IM is installed). The RS3 will
then generate the alarm “RIOB Hardware: Comm Timeout”.