Specifications

RN: 5-77
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
Description: Table 6.4.7 on page 6-4 -35 was modified for the new
MAI32 FIM
.
Table 6.4.7. MAI32 Termination Panel Jumpers
Jumper
Position Effect
HDL01--HDL16
H
D
R
0
1
H
D
R
1
6
Full left
System-powered input point
HDR01--HDR16
Point Type
Full right
Self-powered input point
One jumper
A--C at 1--2
Cage address for Left Group of points L01--L16
(A is recommended)
HD33
ADDRESS
One jumper
B--D at 1--2
Cage address for Right Group of points
R01--R16 (B is recommended)
Pat1--2
Required for correct parity*
HD34
L
O
O
P
P
W
R
ENABLE
Enables detection of loop power loss
L
O
O
PPWR
DETECT
DISABLE
Disables detection of loop power loss
SH and CH connected
All field wiring shields are connected to panel
chassis ground
TB21
Shield Grounding
SH and CH open
All field wiring shields are connected together
and are floating with respect to panel chassis
ground
SH connected to external
ground
All field wiring shields are connected together
and are connected to the external ground point
* Not required for MAI32 FIM 10P58300005.
Description: Clarification and the part numbers for the new MAIO16
and MAI32 FIMs were added to page 6-4-42 (including Table 6.4.10).
MAIO FIMs
Multipoint Analog FIMs are available for 16-point input or output and for
32-point input.
There are three types of 16-point input FIMs:
D
MAIO16 Field Interface Module (FIM) CE Approved --
Redundant:
4--20 mA Input 16 Point 10P54040004 or
10P57700005
D
MAIO Field Interface Module (FIM) -- Redundant:
4--20 mA Input 1984--4414--1001
D
MAIO Field Interface Module (FIM) -- Nonredundant:
4--20 mA Input 1984--4414--0001
(FIM redundancy not supported)