Specifications

RN: 5-59
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
I/O BLOCK CONFIGURATION 06-Aug-98 09:40:30
Address =1G006 Device Type PLCB
Block Tag Block Type PLCB Mode AUTO
Auto Lock no
Source PLCMux/F
Addr 1G-01/F Data Type S int PLC write Mask FFFFx
Value From Source 0. Sample Time 1 S Value to PLC 0000x
Write filter Sim
Tag PortA PLC number 1
Addr
Value From PLC 0.
ponmlkjihgfedcba 0000x Read filter PLC Word Address 040006
Hardware Alarm Code 0 Plant Unit 0 Alarm Priority 0
Figure 9.3.3D. Controlled PLC Register Read and Write
Description: Changes to Table 9.3.9 are a result of additional block
configuration fields and allowable entries being added under this topic
(pages 9-3-14 and 9-3 -15).
Configuring an I/O Block to Read a PLC Register Address
Table 9.3.9. PLCB I/O Block Configuration Fields
Field
Access
Level
Description Allowable Entries
(1)
Block T ype
CONF
T ype of input/output block.
NONE,AIB,CIB,
AOB, COB DIB,
DOB, ADS, PLCB,
MIB, SIB, RIOB,
VIB, PIOB, TIB,
HOB
Mode
SUPV
Current block mode:
If “AUTO”, the block function drives the block
output.
If “SIMULATE”, a ControlBlock simulates the PLC
address register and the block functions drive the
block output.
If “FAIL”, a PLC device is not connected to or
communicating with the PLCB.
AUTO,SIMULATE,