Specifications
RN: 5-51
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
I/O BLOCK CONFIGURATION 18-Jan-92 11:58:59
Address=2AA401 Device Type AIB
Block Tag⇒ Block Type ⇒RIOB Mode → AUTO
Auto Lock ⇒ no
Redundancy Scheme >3/1
Cage Line A1 A2 A3 A4 A5 A6 A7 A8
Backup ⇒ YES ⇒ YES ⇒ NO
Health GOOD GOOD
Xfer Health GOOD
Backup Status READY READY FREE R-4 FREE FREE FREE FREE
Reset Backup of Line 2 (press enter)
Force Backup on Number >0 (none)
Alarm Priority ⇒0 Plant Unit ⇒0
FIC Type AIO Rev 2.1 HW Alarm Code 0
CONFIG 1
Figure 5.1.3. RIOB Configuration Screen—Backing Up FICs
IO-5: Section 3 (Hints for Configuring RIOBs)
Description: The following paragraph was added under the
configuration tip “Configuring the RIOB mode” on page 5-3-2.
Configuring an RIOB must be on point 1 and on an even line.
Configuring a 7/1 RIOB must be on line 8. Configuring a 3/1 RIOB
must be on line 4 or on line 8.
IO: Chapter 8 (Configuring Smart Blocks)
IO-8: Section 1 (Configuring SIBs and VIBs)
Description: The following paragraphs and Table 8.1.1 were added
under the subsection “Using Digital PV” on page 8-1-8.
FIMs have only one HART modem for communication with the 1--32
HART devices. As more devices are added to a FIM, the interval of time
between digital PV updates increases. Table 8.1.1 lists approximate
update rates on an MAI FIM that has 16 attached devices.