Specifications
RN: 5-18
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
REPORT CONFIGURATION 28-Aug-98 14:18:04
****************** START OF REPORT ******************
Detail :⇒y
Type :⇒trend log Color :⇒1n white Row :⇒38 Col :⇒15 Time : ⇒y
Data : ⇒y
File Name:⇒trf1 Node :⇒28 Scaled :⇒100 CREATE DELETE Mean :⇒y ⇒y
Total :⇒y ⇒y
Tag ⇒TREND 2/PV Accum :⇒none Inter :⇒5 secs Minimum:⇒y ⇒y
Maximum ⇒y ⇒y
Time :⇒10:50:00 Duration :⇒10 mins MM Time:⇒y
CONFIG 1
Select trend log as the object type.
CREATEmustbeusedtocreate
or to modify a trend log object.
Figure 4.4.19. Report Configuration Screen with Trend Log Object
Description: The “Trend Node” field was changed to “Node” and the
description of the Time field in Table 4.4.4 was m odified (page 4-4-29).
Table 4.4.4. T rend Log Field Description (continued)
Field
Description
Node
Node on which the trend file resides.
Time
The beginning time of the trend log data that is included in the report. The time can
be entered in the following ways:
NOTE: You can enter a maximum of eight characters. When you specify a relative
value for day or time, you will not be able to specify seconds and you may be limited
as to the number of characters available to specify minutes.
--DD/HH:MM:SS specifies a start time relative to the day or the generation of the
report--for example, --2/10:15 specifies that the report includes
trend log data starting 2 days, 10 hours, and 15 minutes before
the generation of the report.
HH:MM:SS specifies at time—for example, 16:00:00 specifies that the report
includes trend log data starting at 4 P.M.
-- HH:MM:SS specifies an amount of time prior to generation of the report—for
example, --8:00:00 specifies that the report includes trend log data
starting 8 hours before the report generation time.
block variable specifies a number of seconds previous to the report generation
time—for example, a block variable with a value of 120 specifies
that the report includes trend log data starting 120 seconds before
the report generation time.