Specifications
RN: 5-12
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
Customizing the Plant Configuration Backup
You can customize the backup of plant configurations using the BackUp
Plant Config (BUP) command line option, which displays the Backup
Plant Config screen.
Within the Backup Plant Config screen, you can:
D
Select/deselect particular nodes to be backed up (from 1 to 992)
D
Specify the first five characters for the destination file(s)
D
Enter a maximum revision letter (from A to Z )
D
Write the backup plant configuration file to disk.
For more information, refer to the Disk and Tape Manual, DT: 2--4.
CC-2: New Section (Link Editor)
Description: Replace the information in CC--3: Section 3, pages 3--3--9
through 3--3--12 with the following, and move it to CC--2:
Link Editor
The Link Editor allows you to change the addresses of links within
various files to allow them to transfer configurations from one address
range to another.
There are two cases where this is often required:
D
If the node number is re -addressed to another node number for
some reason (including being moved to a different Peerway
Number).
D
If a configuration or range of blocks for a section of the plant is
copied to another area. For example, if two boiler configurations
are similar, once the first configuration is completed, the second
configuration may be copied from the first.
The Link Edit function allows the following operations for file
configurations:
D
Moving or copying from one ControlFile to another ControlFile
Example: move =3 to =31 or move =3 to =294
D
Moving or copying from one controller to another controller
Example: move =3A to =3B or move =3A to =31A
D
Moving an address range within a controller
Example: move range of =3AA101,=3AA832 to starting address
=3BA101 or move =3A--1,5 to starting at address =31A --10 to
=31A --14
Yo u can change the following configurations on the Link Editor screen: