Specifications
RN: 5-4
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
Description: Table 2.5 on page 2-5 was changed to read as follows.
Table 2.5. Output Device Status Message Descriptions
Code
Description
Field Device Malfunction 1000 0000
Field device malfunction; Cleared by field
device self-test.
Field Device Configuration
Changed 0100 0000
Configuration has been changed by the
user . Cleared by user command and
RESET.
Cold Start 0010 0000 Reset sequence executed; on power-up
More Status Available 0001 0000
More status information is available than
can be returned in an Upload Xmtr Config
command. See the Diagnostic Status
field on the Transmitter Status screen.
No Response to Analog
Input 0000 1000
Rev 5 device and higher gets set when
device doesn’t respond to analog current.
Analog Input Current
Saturated 0000 0100
Analog input saturated. Indicates the
4--20mA variable exceeds the
user-configured lower or upper limit or
cutoff values. This error clears
automatically when variable is within
operating limits.
Internal Sensor Out of
Limits 0000 0010
A field device internal sensor exceeds its
operating limits. This error is cleared
automatically when all sensors are within
operating limits.
Variable Out of Range 0000 0001
An active measured variable exceeds its
user-configured range.
AL: Sections 3 and 4 (Alarm Messages in Alphabetical and
Numerical Order)
AL: Chapters 3 and 4
Description: Add the following alarm information where appropriate.
Alarm 112 results in the redundant CP restarting.
No. Message Description List Alarm Area
112
NV Mem Backup
Reset
The CP program was restarted to overcome the
problem where the backup was stuck on one
Controller Processor.
S ControlFile