Specifications

RN: 5-3
RS3: Software Release Notes for P1 R4.2
Changes to RS3 Manuals
CB DISCRETE DIAGRAM 08-Oct-98 12:14:31
Tag Agitator 155 Descriptor Block_Descriptor
Addr -1A-01 Function DISC Discrete Block Plnt>0
Free Space: Stat = 91 % Dyn = 88 % Priority>0
+------------------CONDITIONS---------------------+Step>a
>Level 1 |@c * |
Off OFF | * a= > |Mode>Auto
| * |MsgPr
>Level 2/c |@e * Set >@c & @e |>*14
Off OFF | * |Off
| *Clear>@b |
>Tank 4 |@b * |> FORWARD
on off |---*------------------ACTIONS--------------------|
| * |Event
>Tank 25 |B * Rise> |Type>244
.65 gal | * |
| * ON >B=.65 |Rpt>Adv
|* |
| * Fall> |When>Rise
|* |
| * OFF >B=0 |Log >A
+-------------------------------------------------+
Steps in Manual Block Mode> AUTO
1DA103 NONE Hardware: Comm Timeout HM U
Figure 1.2B. CB Discrete Diagram
AL: Section 2 (Smart Device Alarm Messages)
Description: Table 2.4 on page 2-4 was changed to read as follows.
Table 2.4. Transmitter Status Error Messages Generated by the Transmitter
Message
Description
Xmtr Failure 1000 0000
A hardware error or failure has been detected. See the Diagnostic
Status field on the Transmitter Status screen.
Xmtr Config Changed 0100 0000 A write or set command has been executed.
Cold Start 0010 0000
Power has been turned off and then on, reinstalling the setup
information.
More Status Available 0001 0000
More status information is available than can be returned in an Upload
Xmtr Config command. See the Diagnostic Status field on the
T ransmitter Status screen.
Fixed Current Mode 0000 1000
Primary variable current readings are held at the requested value. The
digital PV is still valid.
Output Current
Saturated 0000 0100
Primary variable is reading above 20 mA or below 4 mA.
Non PV out of Limits 0000 0010 A Non-Primary variable value is out of the transmitter limits.
PV Out of Xmtr Limits 0000 0001 Primary variable is out of the transmitter operating limits.