INVERTER Plug-in option FR-A7AY INSTRUCTION MANUAL Analog output function PRE-OPERATION INSTRUCTIONS 1 INSTALLATION AND WIRING 2 PARAMETER LIST 3 EXTENSION ANALOG OUTPUT 4 DIGITAL OUTPUT 5 Digital output function
Thank you for choosing this Mitsubishi Inverter plug-in option. This instruction manual gives handling information and precautions for use of this equipment. Incorrect handling might cause an unexpected fault. Before using the equipment, please read this manual carefully to use the equipment to its optimum. Please forward this manual to the end user.
) Usage 2. Injury Prevention WARNING CAUTION • Apply only the voltage specified in the instruction manual to each terminal. Otherwise, burst, damage, etc. may occur. • Ensure that the cables are connected to the correct terminals. Otherwise, burst, damage, etc. may occur. • Always make sure that polarity is correct to prevent damage, etc. Otherwise, burst, damage may occur. • While power is on or for some time after power-off, do not touch the inverter as it is hot and you may get burnt. 3.
CONTENTS 1 PRE-OPERATION INSTRUCTIONS 1.1 Unpacking and Product Confirmation .............................................................................................1 1.1.1 1.1.2 1.1.3 2 Packing confirmation ...................................................................................................................................... 1 Parts .................................................................................................................................................
5.1 5.2 5.3 5.4 II DIGITAL OUTPUT 21 Internal Block Diagram....................................................................................................................21 Terminals ..........................................................................................................................................22 Digital Output Function Parameter List .........................................................................................23 Output Signal List ...........................
1 PRE-OPERATION INSTRUCTIONS 1.1 Unpacking and Product Confirmation Take the plug-in option out of the package, check the unit name, and confirm that the product is as you ordered and intact. This product is a plug-in option dedicated for the FR-F700 series. 1.1.1 Packing confirmation Check the enclosed items. Plug-in option Mounting screw (M3 × 6mm) Hex-head screw for option ......................................... 1 .............. 2 (Refer to page 6.) mounting (5.5mm) ...............
PRE-OPERATION INSTRUCTIONS 1.1.2 Parts Terminal block Front view Mounting hole 2 Rear view Connector Connect to the inverter option slot (Refer to page 6.
PRE-OPERATION INSTRUCTIONS 1.1.3 Specifications (1) Output signals Voltage output (across terminals AM0-AMC) 0 to 10VMAXDC Current output (across terminals AM1-AMC) 0 to 20mADC (2) Output resolution Voltage output 3mV Current output 10µA (3) Output accuracy (reference value) ±10% of the full-scale output value Depends on the output signal type.
MEMO 4
2 INSTALLATION AND WIRING 2.1 Pre-Installation Instructions Make sure that the input power of the inverter is off. CAUTION With input power on, do not install or remove the plug-in option. Otherwise, the inverter and plug-in option may be damaged.
INSTALLATION AND WIRING 2.2 Installation Procedure 1) Screw hole for option mounting Inverter side option connector Screw hole for option mounting (on earth plate) Hex-head screw for option mounting 2) 3) 1) Remove the inverter front cover. 2) Mount the hex-head screw for option mounting into the inverter screw hole (on earth plate). (size 5.5mm, tightening torque 0.56N⋅m to 0.75N⋅m) 3) Securely fit the connector of the plug-in option to the inverter connector along the guides.
INSTALLATION AND WIRING 2.3 Wiring (1) Strip off the sheath of the cable to wire. Strip off the sheath about the size below. If the length of the sheath pealed is too long, a short circuit may occur among neighboring wires. If the length is too short, wires might come off. Wire the stripped cable after twisting it to prevent it from becoming loose. Cable stripping size In addition, do not solder it. Use a bar type terminal as required.
INSTALLATION AND WIRING (3) For wiring of the 30K(00620 (EC Version)) or less, route wires between the control circuit terminal block and front cover. If cables can not be routed between the control circuit terminal block and front cover due to the increased number of cables, remove a hook of the front cover and use a space become available. For wiring of the 37K(00770 (EC Version)) or more, use the space on the left side of the control circuit terminal block.
3 PARAMETER LIST When the FR-A7AY is mounted on the inverter, the following parameters are extended.
PARAMETER LIST DIGITAL OUTPUT Parameter Number 10 Name 313 314 315 316 317 DO0 DO1 DO2 DO3 DO4 output selection output selection output selection output selection output selection 318 319 DO5 output selection DO6 output selection Setting Range 0 to 5, (7), 8, 10 to 19, 25, 26, 45 to 47, 64, 70, (71 to 78), 86 to 96, 98, 99, 100 to 105, (107), 108, 110 to 116, 125, 126, 145 to 147, 164, 170, 186 to 196, 198, 199, 9999 Minimum Initial Increments Value 1 9999 Refer to Page 21 and later
4 EXTENSION ANALOG OUTPUT 4.1 Wiring Example By setting the Pr. 306 to Pr. 312 values, analog signals such as the output frequency and output current can be output from the voltage output terminal (AM0) and current output terminal (AM1). Connect the voltmeter or ammeter as shown below: MCCB Power supply (Voltmeter) Inverter Motor IM + 0 to 10VDC FR-A7AY - (Ammeter) AM0 AM1 AMC + 0 to 20 mADC - CAUTION The wiring length between the FR-A7AY and the voltmeter/ammeter should be 10m maximum.
EXTENSION ANALOG OUTPUT 4.2 Internal Block Diagram The following is the internal block diagram about the FR-A7AY analog output function.
EXTENSION ANALOG OUTPUT 4.3 Terminals Terminal Symbol AM0 AMC NC SE Y3 Y4 Y5 Y6 AM0 AM1 NC SE Y0 Y1 Y2 AM1 AMC Y0 to Y6 SE NC (empty) Terminal Name Voltage output terminal Current output terminal Common terminal Description Connect a DC voltmeter (10VDC). Connect a DC ammeter (20mADC). Common to AM0 and AM1 Used for analog output function. (Refer to page 21 ) Do not use.
EXTENSION ANALOG OUTPUT 4.
EXTENSION ANALOG OUTPUT 4.5 Adjustment Procedure 4.5.1 Setting of analog output signal voltage/current switchover (Pr. 309) Use Pr. 309 Analog output signal voltage/current switchover to select whether to output the same signal or different signals from terminal AM0 (voltage output) and terminal AM1(current output). Pr. 309 Setting 0 (initial value) 10 Description Terminal Parameters for Setting Same select signals are output from the voltage output terminal (AM0) and current output terminal (AM1).
EXTENSION ANALOG OUTPUT 4.5.2 Calibration of meter (1) Outputting the same select signals from terminals AM0 and AM1 (Pr. 309 = 0 or 10) START Connect a DC voltmeter (or DC ammeter) across terminals AM0 (or terminal AM1) and AMC. Use Pr. 323 (Pr. 324) to calibrate the meter when the voltage (current) input is 0. Set "21" (reference voltage output) in Pr. 306. At this time, check that the polarity is correct If the meter needle does not point to 0 when voltage or current input is 0, use Pr.
EXTENSION ANALOG OUTPUT (2) Outputting different select signals from terminals AM0 and AM1 (Pr. 309 = 1 or 11) START Connect a DC voltmeter (or DC ammeter) across terminals AM0 (or terminal AM1) and AMC. Use Pr. 323 (or Pr. 324) to calibrate the meter when the voltage (current) input is 0. Set "21" (reference voltage output) in Pr. 306 and Pr. 310.
EXTENSION ANALOG OUTPUT 4.5.3 Output signal setting Set the output signals to be monitored. Set Pr. 306 to output the same signal from terminals AM0 and AM1 and Pr. 306 and Pr. 310 to output different signals. For details of signal definitions, refer to Pr. 54 and Pr. 158 of the inverter manual (applied). Pr. 306/Pr.
EXTENSION ANALOG OUTPUT 4.5.4 Analog signal adjustment [Pr. 307, Pr. 308, Pr. 311, Pr. 312] Use Pr. 307 or Pr. 311 to set for zero analog output (meter points 0). In addition, use Pr. 308 or Pr. 312 to set for maximum analog output (full-scale). Use Pr. 307 to set the value for zero analog output and Pr. 308 for maximum analog output when outputting the same signal from terminals AM0 and AM1. Use Pr. 307(AM1) and Pr. 311(AM0) to set the value for zero analog output and Pr. 308(AM1) and Pr.
EXTENSION ANALOG OUTPUT 4.6 Instructions (1) A voltmeter having smaller internal impedance (or an ammeter having larger internal impedance) than the value indicated in the Specifications may not deflect to full-scale and may not be calibrated. (2) When calibrating a meter which has a small full-scale value, set the output of terminal AM0 (or AM1) to the minimum without the meter connected. Then, connect the meter and make calibration.
5 DIGITAL OUTPUT 5.
DIGITAL OUTPUT 5.2 Terminals By setting the Pr. 313 to Pr. 319 values, output signals available with an inverter as standard can be output from the open collector terminals. (1) Open collector output specifications: Permissible load 24V, 0.1ADC (2) The circuit logic is the same as that of the inverter. For details of changing the control logic, refer to the inverter manual (basic).
DIGITAL OUTPUT 5.
DIGITAL OUTPUT 5.4 Output Signal List For details of signal definitions, refer to Pr. 190 to Pr. 196 Output terminal function selection of the inverter manual (applied).
DIGITAL OUTPUT Setting Signal Name Positive Logic Negative Logic 72 RO2 73 RO3 74 RO4 75 RIO1 76 RIO2 77 RIO3 78 RIO4 86 87 88 89 186 187 188 189 Y86 Y87 Y88 Y89 *1 *2 *3 Setting Function Commercial-power supply side motor 2 connection RO2 *2 Commercial-power supply side motor 3 connection RO3 *2 Commercial-power supply side motor 4 connection RO4 *2 Inverter side motor 1 connection RIO1 *2 Inverter side motor 2 connection RIO2 *2 Inverter side motor 3 connection R
REVISIONS *The manual number is given on the bottom left of the back cover.