Constellation ES.3 SAS Product Manual, Rev. F 52
10.2 Cooling
Cabinet cooling must be designed by the customer so that the ambient temperature immediately surrounding the drive will not
exceed temperature conditions specified in Section 6.5.1, "Temperature."
The rack, cabinet, or drawer environment for the drive must provide heat removal from the electronics and head and disk assembly
(HDA). Users should confirm that adequate heat removal is provided using the temperature measurement guidelines described in
Section 6.5.1.
Forced air flow may be required to keep temperatures at or below the temperatures specified in Section 6.5.1 in which case the drive
should be oriented, or air flow directed, so that the least amount of air flow resistance is created while providing air flow to the
electronics and HDA. Also, the shortest possible path between the air inlet and exit should be chosen to minimize the travel length of
air heated by the drive and other heat sources within the rack, cabinet, or drawer environment.
If forced air is determined to be necessary, possible air-flow patterns are shown in Figure 18. The air-flow patterns are created by one
or more fans, either forcing or drawing air as shown in the illustrations. Conduction, convection, or other forced air-flow patterns are
acceptable as long as the temperature measurement guidelines of Section 6.5.1 are met.
Figure 18. Air flow
Note
Image is for reference only, may not represent actual drive.
Above unit
Under unit
Note. Air flows in the direction shown (back to front)
or in reverse direction (front to back)
Above unit
Under unit
Note. Air flows in the direction shown or
in reverse direction (side to side)