User Manual
SCSI Commands Reference Manual, Rev. J 322
www.seagate.com Parameters for direct access devices
value of the HIGH OPERATING TEMPERATURE LIMIT TRIGGER field, then the device server shall report an informational exception condition with
the additional sense code set to WARNING - HIGH OPERATING TEMPERATURE LIMIT EXCEEDED.
HIGH OPERATING TEMPERATURE LIMIT RESET field
The HIGH OPERATING TEMPERATURE LIMIT RESET field indicates the temperature at which the informational exception condition for the asso-
ciated high critical temperature limit, if any, shall be cleared.
LOW OPERATING TEMPERATURE LIMIT RESET field
The LOW OPERATING TEMPERATURE LIMIT RESET field indicates the temperature at which the informational exception condition for the associ-
ated low critical temperature limit, if any, shall be cleared.
LOW OPERATING TEMPERATURE LIMIT TRIGGER field
The LOW OPERATING TEMPERATURE LIMIT TRIGGER field indicates the minimum temperature at this sensor for which the logical unit is capable
of operating continuously without degrading the logical unit's reliability beyond manufacturer accepted limits. If the EWASC bit is set to one in
the Information Exceptions Control mode page (see SBC-4, SSC-4, or SMC-3) and the associated current temperature
(see 5.2.8.2) is less than
the value of the LOW OPERATING TEMPERATURE LIMIT TRIGGER field, then the device server shall report an informational exception condition
with the additional sense code set to WARNING - LOW OPERATING TEMPERATURE LIMIT EXCEEDED.
5.2.7.3 Relative Humidity Limits log parameter
The Relative Humidity Limits log parameter has the format shown in table 292.
PARAMETER CODE field
The PARAMETER CODE field is described in 5.2.2.2.1 and shall be as shown in table 289 for the Temperature Limits log parameters.
PARAMETER LENGTH field
The PARAMETER LENGTH field is described in 5.2.2.2.1 and shall be set as shown in table 292 for the Temperature Limits log parameters.
The relative humidity limit values used in the Relative Humidity Limits log parameters are shown in table 299.
Table 292 Relative Humidity Limits log parameter
Bit
Byte
7 6 5 4 3 2 1 0
0 (MSB)
PARAMETER CODE (see table 289)
1 (LSB)
2 PARAMETER CONTROL BYTE – binary format list log parameter (see 5.2.2.2.2.5)
3 PARAMETER LENGTH (08h)
4 HIGH CRITICAL RELATIVE HUMIDITY LIMIT TRIGGER
5 HIGH CRITICAL RELATIVE HUMIDITY LIMIT RESET
6 LOW CRITICAL RELATIVE HUMIDITY LIMIT RESET
7 LOW CRITICAL RELATIVE HUMIDITY LIMIT TRIGGER
8 HIGH OPERATING RELATIVE HUMIDITY LIMIT TRIGGER
9 HIGH OPERATING RELATIVE HUMIDITY LIMIT RESET
10 LOW OPERATING RELATIVE HUMIDITY LIMIT RESET
11 LOW OPERATING RELATIVE HUMIDITY LIMIT TRIGGER
Table 293 Relative humidity limit values
Value Description
0 to 100
Relative humidity
101 to 254
Reserved
255
No relative humidity limit